background image

Round Fire and Combination Fire Smoke Dampers

3

Preparation of Openings

•  Frame wall openings as shown below (

see Figure 1, 2, & 2A

).

•  Gypsum wall board must be fastened 12 in. (305mm) on center (O.C.) to all stud and runner flanges surrounding 

opening.

•  Prepare opening between studs and sleeve assembly as shown below (

see Figure 3 & 4

).

•  All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance 

Directory) and/or local codes.

Figure 1

12 in.

24 in. o.c.

Maximum

Floor Runner

2 in.

Ceiling Runner

2 Panhead

Screws

24 in. o.c.

Maximum

(metal studs)

24 in. o.c.

Maximum

(metal studs)

16 in. o.c.

Maximum

(wood studs)

16 in. o.c.

Maximum

(wood studs)

2 in.

Figure 2

Second set of studs are not required on openings

36 in. x 36 in. (914mm x 914mm) or smaller.

Metal stud only

Second set of studs are not required on openings

36 in. x 36 in. (914mm x 914mm) or smaller.

Metal stud only

Figure 2A

Содержание DFDR Series

Страница 1: ...eiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Ch...

Страница 2: ...terials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to prevent overspray if wall text...

Страница 3: ...rs must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Figure 1 12 in 24 in o c Maximum Floor Runner 2 in Ceiling Runner 2 Panhead Screws 24 i...

Страница 4: ...assembly to allow for this expansion The wall floor opening must be a minimum of 7 8 in 22mm larger than the outside diameter of the damper Clearances Required Between Damper Sleeves and Wall Floor O...

Страница 5: ...ITION INDICATOR AND OR ELECTRIC LINK DUCT CONNECTION AREA 2 00 IN 1 50 IN Optional Second Retaining Plate Do not place retainer plate in this groove Figure 5 FSDR SEFSDR SSFSDR Inserting Damper into W...

Страница 6: ...p for easy installation when the clamping screw is loosened If necessary remove the clamping screw and nut see Figure 7 Position the retaining plate between the blade axle and the actuator shaft as sh...

Страница 7: ...ensor with the lower temperature setting can be bypassed by an external contact closure allowing the damper to reopen until the secondary temperature is reached the sensor with the higher temperature...

Страница 8: ...he latest editions of NFPA 80 90A 92 101 105 UL864 AMCA 503 03 and local codes Actuator manufacturer recommendations Damper Troubleshooting The following is a possible cause and correction list for co...

Отзывы:

Похожие инструкции для DFDR Series