- 30 -

User Manual Digital Heat Regulators

English

� 

During the installation and operation of the instrument, follow the 

instructions set out below:

1) The instrument should be installed by a skilled operator. 

2) Strictly follow the connection diagrams when installing the instrument.

3)  Do not power or connect the instrument if any part of it is damaged.

4)  Before touching the terminals, make sure the wires to be connected to 

the instrument are not live.

5)  The connection cables should be able to resist the maximum operating

temperature (Tmax), obtained from the sum of the maximum ambient 

temperature (Ta) + a temperature of 20 °C (Tmax= Ta + 20 °C).

6)  The instruments guarantee a main insulation between the low voltage 

(250 V) and very low voltage parts. 

7)  Any outside switches connected to the controls should guarantee a 

minimum insulation at operating temperature of 250 V AC, or should be

protected by equivalent insulation.

8)  Contacts: all type 1C (CEI 107-70 and variants).

9)  The instruments require no maintenance.

Series of digital temperature regulators satisfying the simplest requirements in 

the field of heat regulation. They can be used as heating or refrigeration regulators

and as maximum/minimum alarms.

� 

Three dedicated base models for probe input:

- PTC thermal resistances

(

P

os.

T

emp.

C

oeff.) - Ni100, Pt100

HT

NiPt

- NTC thermal resistances

(

N

egative 

T

emperature 

C

oefficient)    

HT

NTC

- TC thermocouples

- J, K, L, R, S, T, E, N

HT

JK

• For each single model, the probe input can be configured from the keyboard.

• Two probe inputs for the HT 

NTC

models, for the measurement of two temperatures

that can be displayed alternatively by the closure or opening of an outer consensus

to be connected to the instrument, or directly from the keyboard for the 72x72 mm 

rear panel version (this version has no digital input).

• Available in versions with 1 or 2 relay outputs with exchange contact.

• Heat regulators with 3 digit, seven segment and decimal point display.

• Relay intervention signalling lamp.

• Temperature T2 signalling lamp (only models HT 

NTC

-..P7.. and HT 

NTC

-..D..)

• Display range: -99 ÷ +999 °C

• Display resolution: 0.1 °C (-9,9 ÷ +99.9 °C) and 1 °C (< -9.9 °C and > +99.9 °C)

• Precision: ±0.5 % of the end of scale value ±1 digit 

(at an ambient temperature of 23 °C)

• Sampling time: 0.5s

TECHNICAL SPECIFICATIONS

SAFETY WARNINGS

- 31 -

User Manual Digital Heat Regulators

English

• Digital parameter setting:

- Set point

-  Differential

-  Neutral zone

-  Output drive times

-  Digital input function and delay time 

- Alarm delay / buzzer enable time

-  Probe calibration offset

-  Resolution displayed

-  Temperature measurement unit

-  Measurement display filter (update speed)

-  Probe input type

-  Password 

-  Operating modes (regulation):

—  ON/OFF direct and/or reverse action with or without neutral zone

— PWM direct and reverse action and neutral zone

— ALARM

— Refrigeration mode

— Special mode

• 2 independent set points

• Digital input: 1 (not versions HT 

NiPt

-..P7A, HT 

NTC

-P7A, HT 

JK

-..P7A) for outside

consensus for configurable function: outside alarm, regulation ON/OFF, selection 

of probe to be displayed, set point switching, direct/reverse switching, etc 

• Acoustic and visual alarm signals for: outside alarm (from digital input),

probe alarm (malfunction), minimum or maximum alarm

• Infrared receiver with RC-5 protocol (not versions HT 

NTC

-1DA, HT 

NTC

-2DA) for

remote control (accessory available separately for remote programming)

• Available in the following fixing versions: rear panel 33x75 mm,

rear panel 72x72 mm and modular 4 DIN

• Power supply: see table on the following page

• Rated power output: 3 VA for the rear panel 33x75 mm versions

4.5 VA for the rear panel 72x72 mm and modular 4 DIN versions

• Max absorption: 100 mA at 12 V  50 mA at 24 V  (1 channel)

• Operating temperature: 0 ÷ +50 °C

• Operating humidity: <80% 

• Storage temperature: -10 ÷ +70 °C (<80% RH)

• Protection level: front panel IP54 (IP40 for the 4 DIN module version) 

terminals IP20

En

gl

is

h

Содержание HT NiPt Series

Страница 1: ......

Страница 2: ......

Страница 3: ...ectrical connections Page 33 Glossary Page 34 Operation Page 39 Setting the regulation parameters Page 39 Parameter menu Page 41 Error messages Page 48 Reference standards Page 49 Dimensions and conne...

Страница 4: ...regulators satisfying the simplest requirements in the field of heat regulation They can be used as heating or refrigeration regulators and as maximum minimum alarms Three dedicated base models for p...

Страница 5: ...regulation ON OFF selection of probe to be displayed set point switching direct reverse switching etc Acoustic and visual alarm signals for outside alarm from digital input probe alarm malfunction min...

Страница 6: ...YES YES VM643400 HT JK 2P3D from 12 to 24 V AC DC 10 2 YES YES Rear panel 72x72 mm Code Model Power supply Power supply n of Digital Infrared tollerance relays input receiver VM625100 HT NiPt 1P7A 24...

Страница 7: ...ting to become ON due to an active timing Out 2 LED off if relay two is OFF on if relay two is ON flashing if relay two in OFF is waiting to become ON due to an active timing Keys Three parameter sett...

Страница 8: ...ucing the temperature Reverse action A regulator acts in reverse mode when it limits the reduction of the measurement controlled For example in a heating system the reduction in temperature correspond...

Страница 9: ...point If both outputs are used the hysteresis for each output is equivalent to half the differential In this case output 1 will be activated when the measurement controlled reaches the value ST1 DF1...

Страница 10: ...or both outputs In this operating mode the relays are activated impulsively with an interval that can be set on the basis of the TCL value see the output menu Within this interval the relay will stay...

Страница 11: ...fferential 1 if the digital input is open and set point 2 differential 2 if closed The operating modes are the same as mode 0 It is necessary to set both the set point ST1 and ST2 differential DF1 and...

Страница 12: ...and differential 2 PRO 9 respectively In this mode output 1 operates in reverse and output 2 in direct It is necessary to set the values of set point 1 ST1 and differential 1 DF1 for output 1 and set...

Страница 13: ...sor The status of outputs OUT1 and OUT2 There are two types of programming for the setting of the regulation parameters Simplified programming Advanced programming Note to reset the default values set...

Страница 14: ...entered correctly the label of the first menu will appear Otherwise the system will return to normal status Advanced programming Access is gained to advanced programming from normal status by pressin...

Страница 15: ...ing the changes made Note During the display and modification of the parameters the instrument will continue to operate with the previously set parameters If password 2 is enabled access password for...

Страница 16: ...onnected to the instrument this parameter is frequently used for compressors for example 5 the minimum time for which the output should remain ON 6 timing enabled for relay 1 output only OFF Labels of...

Страница 17: ...S1 contact open probe S0 contact closed probe S1 The digital input function is excluded when one of the following operating modes is selected inside the system menu SYS mode 6 mode 7 and mode 8 10 Thi...

Страница 18: ...ent unit is modified the parameters set are not con verted automatically but have to be re calibrated Labels of parameters that can be modified Description Parameter values default notes SUA Output st...

Страница 19: ...t to this parameter by default It corresponds to the use of temperature sensor NTC code VN870200 see Red Line catalogue under the item Heat Regulation Temperature Probes For the use of sensors other t...

Страница 20: ...ft of the set point 2 neutral zone with channel 1 in reverse and channel 2 in direct with set point 1 and differential 1 3 as mode 0 but with differential centred on the set point 4 as mode 1 but with...

Страница 21: ...switching between set point 1 differential 1 and set point 2 differential 2 through digital input open set 1 closed set 2 5 output associated with maximum alarm for set point 2 6 output associated wit...

Страница 22: ...ating mode Parameter 0 1 2 3 4 5 6 7 8 9 10 IN0 50 50 100 0 0 100 50 50 100 100 DF0 50 50 100 50 50 100 50 50 100 100 IN1 100 100 100 50 50 100 100 100 100 0 DF1 50 50 100 50 50 100 50 50 100 100 The...

Страница 23: ...49 User Manual Digital Heat Regulators English For safety EN 60730 2 9 For electromagnetic compatibility EN 55014 1 EN 55014 2 EN 61000 6 2 EN 61000 6 3 REFERENCE STANDARDS English...

Страница 24: ...e r s up p l y Relay output 8 1 A 250 V Digital input Probe input PTC 3 wires Probe input PTC 2 wires Digital input 6 7 8 9 5 2 3 4 1 6 7 8 9 Connection diagram Model HT NiPt 1P3D HT NTC 1P3D HT JK 1P...

Страница 25: ...put 2 8 1 A 250 V Probe input PTC 3 wires Probe input PTC 2 wires Digital input Relay output 1 8 1 A 250 V Relay output 2 8 1 A 250 V Digital input 14 11 12 13 15 10 16 17 18 5 2 3 4 6 1 7 8 9 16 17 1...

Страница 26: ...5 10 16 17 18 HT JK 1P3A Probe input TC Digital input Relay output 8 1 A 250 V P o wer sup p ly 14 11 12 13 15 10 16 17 18 5 2 3 4 6 1 7 8 9 HT JK 1P3D Probe input TC Digital input Relay output 8 1 A...

Страница 27: ...HT NiPt 1P7A 24 V 5 0 60 H z 230 V 5 0 60 H z Relay output 8 1 A 250 V Probe input PTC 3 wires Probe input PTC 2 wires 4 5 6 1 2 7 11 12 1 4 5 6 HT NiPt 2P7A 24 V 5 0 60 H z 230 V 5 0 60 H z Relay out...

Страница 28: ...6 0 H z 230 V 5 0 6 0 H z NTC1 NTC2 Probe input NTC Relay output 1 8 1 A 250 V Relay output 2 8 1 A 250 V 4 5 6 1 2 3 8 9 7 11 12 10 HT JK 1P7A 24 V 5 0 6 0 H z 230 V 5 0 6 0 H z Probe input TC Relay...

Страница 29: ...60 H z 230 V 5 0 60 H z Digital input Probe input PTC 3 wires Probe input PTC 2 wires Relay output 8 1 A 250 V 5 2 3 4 6 1 14 11 12 13 15 10 7 16 8 9 17 18 16 17 18 HT NiPt 2DA 24 V 5 0 60 H z 230 V 5...

Страница 30: ...input Probe input NTC NTC1 NTC2 Relay output 1 8 1 A 250 V Relay output 2 8 1 A 250 V 5 2 3 4 6 1 14 11 12 13 15 10 7 16 8 9 17 18 HT JK 1DA 24 V 5 0 60 H z 230 V 5 0 60 H z Digital input Probe input...

Страница 31: ......

Страница 32: ...ale di Brugherio I 20047 Brugherio Mi Via Belvedere 11 Phone 39 039 20901 Fax 39 039 2090222 www vemersiber it V3IS00323 010 122006 Vemer S p A I 32032 Feltre BL Via Camp Lonc 16 Tel 39 0439 80638 Fax...

Отзывы: