Description of parameters

• Inside the tables, the labels are presented in the same order as they appear in the

various menus of the instrument.

[REG] regulation menu

Notes:

(1) For values LO1/LO2 and HI1/HI2, see the display menu [DSP]

(2) Parameter active only if the operating mode permits 

[OUT] output menu

Notes:

(3) This parameter enables the handling of the times defined by DON, TOF and TON for

each output channel, in the following ways:

0

timing not enabled for either relay output

1

timing enabled for relay 1 output only

2

timing enabled for relay 2 output only

3

timing enabled for relay 1 and 2 outputs

(4) this parameter limits the number of start-ups per hour for the driver connected to

the instrument (this parameter is frequently used for compressors, for example)

(5) the minimum time for which the output should remain ON

(6) timing enabled for relay 1 output only OFF

Labels of 

parameters that 

can be modified

Description

Parameter

values

default notes

ST1

set-point 1

degrees LO1

HI1

20.0

(1)

DF1

Differential for set-point 1

degrees 0.1

100

2.0

ST2

set-point 2

degrees LO2

HI2

30.0

(2)

DF2

Differential for set-point 2

degrees 0.1

100

2.0

(2)

DBN

Neutral zone (dead band)

degrees

0

100

2.0

(2)

min  max 

unit

Labels of 

parameters that 

can be modified

Description

Parameter

values

default notes

ETR

Handling time on 

relays enabled

-

0

3

3

(3)

DON

Minimum time between 

2 start-ups of the same relay

min

0

200

0

(4)

TOF

Minimum relay ON time

min

0

200

0

(5)

TON

Minimum relay OFF time

min

0

200

0

(6)

INI

Initial delay from start-up 

of instrument

min

0

200

0

(7)

TCL

PWM cycle time

sec

1

200

200

(8)

min  max 

unit

- 43 -

User Manual Digital Heat Regulators

English

(7) the delay time for the driving of the outputs from the instant of instrument reset

(8) the period that can be set for PWM regulation. This item is displayed only if the

operating mode selected is PRO=5 (see system menu).

[ING] outside input menu

Notes:

(9) The values that can be set are:

0

Not active

1

Outside alarm (with contact open) with delay time “DID” and automatic 

reset at the end of the alarm. The output status becomes “SUI”

2

Outside alarm (with contact open) with manual reset

3

The input operates as a switch: instrument on with contact closed and off 

with contact open

4

The input operates as a switch for the display of the two probes S0 and S1

(contact open-probe S0, contact closed-probe S1)

The digital input function is excluded when one of the following 

operating modes is selected inside the system menu [SYS]:

mode=6, mode=7 and mode=8

(10) This is the delay after which the instrument responds to a signal from the digital 

input

(11) When the digital input is active and a time period “DID” has lapsed,

the outputs take on the following states:

0

Both relays OFF

1

Relay 1 ON and relay 2 OFF

2

Relay 1 OFF and relay 2 ON

3

Both relays ON

(12) This is the variation of the “Set” in degrees when the instrument switches 

to night operation

Labels of 

parameters that 

can be modified

Description

Parameter

values

default notes

TID

Digital input function

-

0

4

0

(9)

DID

Digital input delay

min

0

200

0

(10)

SUI

Output status with digital

input active (open)

-

0

3

0

(11)

DEL

Variation in night-time 

temperature

degrees -50.0 +50.0

5.0

(12)

min  max 

unit

En

gl

is

h

Содержание HT NiPt Series

Страница 1: ......

Страница 2: ......

Страница 3: ...ectrical connections Page 33 Glossary Page 34 Operation Page 39 Setting the regulation parameters Page 39 Parameter menu Page 41 Error messages Page 48 Reference standards Page 49 Dimensions and conne...

Страница 4: ...regulators satisfying the simplest requirements in the field of heat regulation They can be used as heating or refrigeration regulators and as maximum minimum alarms Three dedicated base models for p...

Страница 5: ...regulation ON OFF selection of probe to be displayed set point switching direct reverse switching etc Acoustic and visual alarm signals for outside alarm from digital input probe alarm malfunction min...

Страница 6: ...YES YES VM643400 HT JK 2P3D from 12 to 24 V AC DC 10 2 YES YES Rear panel 72x72 mm Code Model Power supply Power supply n of Digital Infrared tollerance relays input receiver VM625100 HT NiPt 1P7A 24...

Страница 7: ...ting to become ON due to an active timing Out 2 LED off if relay two is OFF on if relay two is ON flashing if relay two in OFF is waiting to become ON due to an active timing Keys Three parameter sett...

Страница 8: ...ucing the temperature Reverse action A regulator acts in reverse mode when it limits the reduction of the measurement controlled For example in a heating system the reduction in temperature correspond...

Страница 9: ...point If both outputs are used the hysteresis for each output is equivalent to half the differential In this case output 1 will be activated when the measurement controlled reaches the value ST1 DF1...

Страница 10: ...or both outputs In this operating mode the relays are activated impulsively with an interval that can be set on the basis of the TCL value see the output menu Within this interval the relay will stay...

Страница 11: ...fferential 1 if the digital input is open and set point 2 differential 2 if closed The operating modes are the same as mode 0 It is necessary to set both the set point ST1 and ST2 differential DF1 and...

Страница 12: ...and differential 2 PRO 9 respectively In this mode output 1 operates in reverse and output 2 in direct It is necessary to set the values of set point 1 ST1 and differential 1 DF1 for output 1 and set...

Страница 13: ...sor The status of outputs OUT1 and OUT2 There are two types of programming for the setting of the regulation parameters Simplified programming Advanced programming Note to reset the default values set...

Страница 14: ...entered correctly the label of the first menu will appear Otherwise the system will return to normal status Advanced programming Access is gained to advanced programming from normal status by pressin...

Страница 15: ...ing the changes made Note During the display and modification of the parameters the instrument will continue to operate with the previously set parameters If password 2 is enabled access password for...

Страница 16: ...onnected to the instrument this parameter is frequently used for compressors for example 5 the minimum time for which the output should remain ON 6 timing enabled for relay 1 output only OFF Labels of...

Страница 17: ...S1 contact open probe S0 contact closed probe S1 The digital input function is excluded when one of the following operating modes is selected inside the system menu SYS mode 6 mode 7 and mode 8 10 Thi...

Страница 18: ...ent unit is modified the parameters set are not con verted automatically but have to be re calibrated Labels of parameters that can be modified Description Parameter values default notes SUA Output st...

Страница 19: ...t to this parameter by default It corresponds to the use of temperature sensor NTC code VN870200 see Red Line catalogue under the item Heat Regulation Temperature Probes For the use of sensors other t...

Страница 20: ...ft of the set point 2 neutral zone with channel 1 in reverse and channel 2 in direct with set point 1 and differential 1 3 as mode 0 but with differential centred on the set point 4 as mode 1 but with...

Страница 21: ...switching between set point 1 differential 1 and set point 2 differential 2 through digital input open set 1 closed set 2 5 output associated with maximum alarm for set point 2 6 output associated wit...

Страница 22: ...ating mode Parameter 0 1 2 3 4 5 6 7 8 9 10 IN0 50 50 100 0 0 100 50 50 100 100 DF0 50 50 100 50 50 100 50 50 100 100 IN1 100 100 100 50 50 100 100 100 100 0 DF1 50 50 100 50 50 100 50 50 100 100 The...

Страница 23: ...49 User Manual Digital Heat Regulators English For safety EN 60730 2 9 For electromagnetic compatibility EN 55014 1 EN 55014 2 EN 61000 6 2 EN 61000 6 3 REFERENCE STANDARDS English...

Страница 24: ...e r s up p l y Relay output 8 1 A 250 V Digital input Probe input PTC 3 wires Probe input PTC 2 wires Digital input 6 7 8 9 5 2 3 4 1 6 7 8 9 Connection diagram Model HT NiPt 1P3D HT NTC 1P3D HT JK 1P...

Страница 25: ...put 2 8 1 A 250 V Probe input PTC 3 wires Probe input PTC 2 wires Digital input Relay output 1 8 1 A 250 V Relay output 2 8 1 A 250 V Digital input 14 11 12 13 15 10 16 17 18 5 2 3 4 6 1 7 8 9 16 17 1...

Страница 26: ...5 10 16 17 18 HT JK 1P3A Probe input TC Digital input Relay output 8 1 A 250 V P o wer sup p ly 14 11 12 13 15 10 16 17 18 5 2 3 4 6 1 7 8 9 HT JK 1P3D Probe input TC Digital input Relay output 8 1 A...

Страница 27: ...HT NiPt 1P7A 24 V 5 0 60 H z 230 V 5 0 60 H z Relay output 8 1 A 250 V Probe input PTC 3 wires Probe input PTC 2 wires 4 5 6 1 2 7 11 12 1 4 5 6 HT NiPt 2P7A 24 V 5 0 60 H z 230 V 5 0 60 H z Relay out...

Страница 28: ...6 0 H z 230 V 5 0 6 0 H z NTC1 NTC2 Probe input NTC Relay output 1 8 1 A 250 V Relay output 2 8 1 A 250 V 4 5 6 1 2 3 8 9 7 11 12 10 HT JK 1P7A 24 V 5 0 6 0 H z 230 V 5 0 6 0 H z Probe input TC Relay...

Страница 29: ...60 H z 230 V 5 0 60 H z Digital input Probe input PTC 3 wires Probe input PTC 2 wires Relay output 8 1 A 250 V 5 2 3 4 6 1 14 11 12 13 15 10 7 16 8 9 17 18 16 17 18 HT NiPt 2DA 24 V 5 0 60 H z 230 V 5...

Страница 30: ...input Probe input NTC NTC1 NTC2 Relay output 1 8 1 A 250 V Relay output 2 8 1 A 250 V 5 2 3 4 6 1 14 11 12 13 15 10 7 16 8 9 17 18 HT JK 1DA 24 V 5 0 60 H z 230 V 5 0 60 H z Digital input Probe input...

Страница 31: ......

Страница 32: ...ale di Brugherio I 20047 Brugherio Mi Via Belvedere 11 Phone 39 039 20901 Fax 39 039 2090222 www vemersiber it V3IS00323 010 122006 Vemer S p A I 32032 Feltre BL Via Camp Lonc 16 Tel 39 0439 80638 Fax...

Отзывы: