TYPE OF REGULATION
The default regulation is of the On-Off type, with the system switched off at the sets
and with fi xed differential of 0.3 °C [0.5 °F]. The
examples set out below are for
winter operation
. The summer operation is complementary, meaning that if the
command is activate for one it is deactivate for the other..
In On-Off operation, if the measurement is less than the minimum threshold the
load is always on. In proportional regulation, the regulation is on a 10 minute time
base, with the following specifi cations:
Tmis
≥
Tset
+ 0.6 °C [1.1 °F]
⁄
relè OFF
Tmis = Tset
+ 0.5 °C [0.9 °F]
⁄
1 minute ON; 9 minutes OFF
Tmis = Tset
+ 0.4 °C [0.7 °F]
⁄
2 minutes ON; 8 minutes OFF
Tmis = Tset
+ 0.3 °C [0.5 °F]
⁄
3 minutes ON; 7 minutes OFF
Tmis = Tset
+ 0.2 °C [0.4 °F]
⁄
4 minutes ON; 6 minutes OFF
Tmis = Tset
+ 0.1 °C [0.2 °F]
⁄
5 minutes ON; 5 minutes OFF
Tmis = Tset
⁄
6 minutes ON; 4 minutes OFF
Tmis = Tset
- 0.1 °C [0.2 °F]
⁄
7 minutes ON; 3 minutes OFF
Tmis = Tset
- 0.2 °C [0.4 °F]
⁄
8 minutes ON; 2 minutes OFF
Tmis = Tset
- 0.3 °C [0.5 °F]
⁄
9 minutes ON; 1 minute OFF
Tmis
≤
Tset
- 0.4 °C [0.7 °F]
⁄
relè ON
If there is a change in the operating set, the regulation takes place in ON-OFF mode
until the
Tset
is reached for the fi rst time, to reach the conditions set more rapidly.
DISPLAY DURING OPERATION
The possible display readings and corresponding operation are set out below..
■
Automatic operation:
weekly clock displaying the hour, minutes and day of
the week; temperature graph, ambient temperature,
symbol
“C”
(default) or
“F”
; symbol
(if the
boiler is active) or symbol
(if the air conditioner
is active).
TYPE OF REGULATION
DISPLAY DURING OPERATION