DEFAULT VALUES
Parameter
min
max
step
default
winter manual setpoint
2.0°C
35.0°C
0.1°C
21°C
summer manual setpoint
2.0°C
35.0°C
0.1°C
25°C
T1 winter
2.0°C
T2
0.1°C
15.0°C
T2 winter
T1
T3
0.1°C
18.0°C
T3 winter
T2
35.0°C
0.1°C
21.0°C
T2 summer
10.0°C
T3
0.1°C
23.0°C
T3 summer
T2
35.0°C
0.1°C
25.0°C
antifreeze temperature
1.0°C
10.0°C
0.1°C
6.0°C
operating mode
winter
summer
-
winter
regulation type
ON/OFF
PROP
-
ON/OFF
ON/OFF differential
0.1°C
1.0°C
0.1°C
0.3°C
proportional band
0.5°C
5.0°C
0.1°C
0.5°C
proportional period
10’
30’
10’
10’
password
0
999
1
000
(deactivated)
winter hour meter
0
1
0
summer hour meter
0
1
0
winter/summer time
ON
OFF
-
ON
winter/summer time
change
Summer:
LAST DAY7
march 02:00
Winter: LAST
DAY7 october
03:00
activation delay
0’
45’
15’
0’
timed operations
0h
99d
1h
0h
Содержание Dafne
Страница 1: ...Digital chronothermostat Dafne User manual ...
Страница 2: ......
Страница 10: ...English 8 Dafne chronothermostat user s manual BATTERY DAFNE MOUNTING Gewiss Chorus series B Remove the cogs ...
Страница 11: ...English 9 Dafne chronothermostat user s manual DAFNE 230 MOUNTING Gewiss Chorus series B Remove the cogs ...
Страница 13: ...English 11 Dafne chronothermostat user s manual DAFNE 230 MOUNTING Bticino Matix series B BM Remove the cogs ...
Страница 14: ...English 12 Dafne chronothermostat user s manual BATTERY DAFNE MOUNTING Vimar Idea series VI B ...
Страница 15: ...English 13 Dafne chronothermostat user s manual DAFNE 230 MOUNTING Vimar Idea series VI B ...
Страница 49: ......
Страница 50: ......
Страница 51: ......