- 55 -
User Manual - CRONO.X programmable thermostat
English
ADVANCED PROGRAMMING
Advanced programming makes it possible to change some parameters and view some
system data.
The user-selectable parameters are:
PARAMETER
READING
DEFAULT PARAMETER RANGE
NOTES
Temperature control
method
rEG
0
0
= ON/OFF
P
= PROPORTIONAL
Control band
(ONLY when
rEG=P and
WINTER-HEATING
operating mode)
bnd
00.5 °C
00.5°C ÷ 05.0°C
Control period
(ONLY when
rEG=P and
WINTER-HEATING
operating mode)
PEr
10 minutes 10 – 20 – 30 minutes
Differential
(ONLY when rEG=O)
dIF
00.3 °C
00.1°C ÷ 01.0 °C
Antifreeze temperature
(only when in
WINTER-HEATING
mode)
0FF
06.0 °C
01.0 °C ÷ 10.0 °C
“---” = disabled
The temperature is
kept pressing the
OFF key
Unit of measurement
deg
C
C=Celsius
F= Fahrenheit
External sensor
ESt
n0
n0
= not provided
YES
= external sensor
is connected
External probe
X.TEMP
code VN883500
(optional)
Control sensor
ONLY when ESt=YES)
SnS
Int
Int
= internal
ESt
= external
RS485 output enabled
(Out Bus)
bUS
YES
YES
= enabled
n0
= disabled
Phone-control output