Terminal box overview

Terminal

box type

Terminal board

I

B max

Q

Bmin

Q

Bmax

Terminal type

Connecting

thread

a

[A]

[mm

2

]

[mm

2

]

[mm]

KA 05-13

KB 5580

27.5

2.5

U-clamp terminal

M4

25 A

KB 3Ex (KS 10A)

53

6

10

slot terminal

S10 x 1

4.3 ± 0.1

63 A

KB 4Ex (KS 14A)

72

10

16

slot terminal

S14 x 1.25

6.3 ± 0.2

100 A

KB 4Ex (KS 14A)

72

10

16

slot terminal

S14 x 1.25

6.3 ± 0.2

200 A

KB 5Ex (KS 18A)

118

25

35

slot terminal

S18 x 1.5

9.2 ± 0.2

25 AV

KL 155

30

4

U-clamp terminal

M5

-

25 AV

KB 5590Ex/d 5,2

35

4

U-clamp terminal

M4

-

63 AV

KB 5121Ex-3

58.5

10

U-clamp terminal

M5

-

100 AV

KB 5121Ex-3

58.5

10

U-clamp terminal

M5

-

100 AV

KB 5130Ex

114

35

U-clamp terminal

M6

-

200 AV

KB 5130Ex

114

35

U-clamp terminal

M6

-

100/63 AV

KM 8/6, VEM 8/6

63

10

Stud/U-clamp terminal*)

M6/M5

-

200 A-SB

KM 10/8, VEM 10/8

100

70

Stud/saddle terminal 

M8/ 2 x M6

-

KB 5130 Ex

118

35

U-clamp terminal

M6

-

400 AV

KM 10/8, VEM 10/8

100

70

Stud/saddle terminal 

M8/2 x M6

-

400 A-SB

KM 10/8, VEM 10/8

100

70

Stud/saddle terminal 

M8/2 x M6

-

KM 16/12, VEM 16/12

250

120

M12/2 x M10

630 A

VEM KLP 630-16

455

35

300

Stud/screw terminal

M16M12/M8

-

1000 A

VEM KLP 1000

1000

70

2 x 240

Current rail

M10

-

K1X 200 A

KM 10/8, VEM 10/8

100

70

Stud/saddle terminal 

M8/2 x M6

-

K2X 200 A

KM 10/8, VEM 10/8

100

70

Stud/saddle terminal 

M8/2 x M6

-

K1X 400 A

KM 16/12, VEM 16/12

250

120

Stud/saddle terminal 

M12/2 x M10

-

K2X 400 A

KM 16/12, VEM 16/12

250

120

Stud/saddle terminal 

M12/2 x M10

-

I

B max

 

max. rated current   

 

 

Q

Bmin

 / Q

Bmax

 

max. rated crosssection

a   

slot width of the slotted bolt (terminal board according to DIN 22412) 

M

Anzug

 

max. tightening torque for connecting thread

*)   

for single-core connection of solid conductors 6…10 mm

2

, connector formed as loop

Thread Ø

S10x1 S14x1,25

S18x1,5

M4

M5

M6

M8

M10

M12

M16

M20

Terminal board (Motor)

-

-

-

1.5

2.5

4

7.5

12.5

-

15

-

Terminal stud

6

10

20

1.2

1.2

3

6

10

15.5

30

52

Screw terminal

7.5

20

U-clamp terminal/ 

saddle terminal

-

-

-

1.2

1.2

3

-

10

-

-

-

Seal for terminal box

Seal

Permitted coolant temperature 

Surface seal, silicon red, 3 mm thick

-40°C

Silicone foam Ø 8 mm white

EPDM E 9566, 3 mm thick *)

EPDM, black, 3 mm thick

-30°C

*) only terminal box KA 05-13

Axial shaft gasket

Series (IE.-)K1.R 112 up to 400, (IE.-)W.1R 112 up to 315, (IE.-)W.2R 400

Seal material

Permitted minimum coolant temperature 

FPM 80, FKM

-25°C

Silicone

-30°C

Tightening torques for connections (DIN 46200)

Содержание IE3-K11R 132S 4 Ex e IIC T3

Страница 1: ...EX ATEX ATEX Additional Installation Operating and Maintenance Instructions Explosion protected three phase asynchronous motors with squirrel cage rotor for low voltage Ident Nr 50229 01 Version 08 20...

Страница 2: ...ark IE is added to the type designation whereas 1 2 3 acc to IEC EN 60034 30 1 Example IE3 K11R 132S 4 Ex e IIC T3 Type of protection increased safety e eb Type of protection n increased safety ec Typ...

Страница 3: ...zones 1 and 2 at least IP 55 for operation in zone 22 and IP 65 for operation in zones 21 and 22 with conducting dust For combinations always the highest required type of protection has to be used The...

Страница 4: ...urface enclosure shaft Motors with double identification are only intended for use in gas or dust explosive atmospheres Use in hybrid mixtures must be checked and approved separately Generally notes f...

Страница 5: ...60034 30 1 is allowed for explosion protected motors Indicated are IE class and rated efficiency The determination of the motor efficiency is done with direct measurement complying with IEC EN 60034 2...

Страница 6: ...ection the standard security and starting instructions are valid The cable glands or screwed sealing plugs must be admitted for use in Exapplications The installation torques sealing areas and clamp r...

Страница 7: ...300 Stud screw terminal M16M12 M8 1000 A VEM KLP 1000 1000 70 2 x 240 Current rail M10 K1X 200 A KM 10 8 VEM 10 8 100 70 Stud saddle terminal M8 2 x M6 K2X 200 A KM 10 8 VEM 10 8 100 70 Stud saddle t...

Страница 8: ...wing of holes 3 The inner earth conductor from the motor green yellow with crimped lug has to be placed under the clamping yoke of the earth connection 4 The outgoing cables of the motor have to be so...

Страница 9: ...ted PTC tripping device and marking II 2 G Do only operate with approved PTC Ther mistor Relays with indication II 2 G Anti condensation heating The heating tapes must comply with the directive 2014 3...

Страница 10: ...t free room if possible If this is not possible suitable measures have to be taken to prohibit that dust can collect inside of the enclosure At disassembly take extra care that the sealing parts like...

Страница 11: ...th life time lubrication From size 315MX upwards they are equipped with relubrica tion devices which can be ordered for smaller motors as option Information about bearings and relubrication can be fou...

Страница 12: ...einforced bearings are supplied with a transportation safety device The transportation safety device at the shaft end must only be removed during installation of the motor and before switching on Turn...

Страница 13: ...x 1 5 50 612 M1 EX 3 6 5 14 5 M 16 x 1 5 50 616 M EX 5 9 17 5 M 20 x 1 5 50 620 M1 EX 6 12 22 7 5 M 20 x 1 5 50 620 M EX 9 13 22 7 5 M 25 x 1 5 50 625 M EX 11 16 27 10 M 32 x 1 5 50 632 M EX 14 21 34...

Страница 14: ...14 08 2017 50229 01 EU Declaration of Conformity according to EU Directive 2014 34 EU...

Страница 15: ...b IIIC TX C Db 0637 II 2G II 2D Ex db IIC T3 T6 or Ex db IIC T3 T6 Gb or Ex d IIC T3 T6 or Ex d IIC T3 T6 Gb or optionally Ex tb IIIC T200 C T85 C Db 0637 II 2G II 2D Ex db eb IIC T3 T6 or Ex db eb II...

Страница 16: ...roup com High voltage department Fon 49 351 208 3237 Fax 49 351 208 1108 E mail high voltage vem group com Drive systems department Fon 49 351 208 1154 Fax 49 351 208 1185 E mail drive systems vem gro...

Отзывы: