•  The control system has been designed for use with genuine VELUX prod-

ucts. Connection to other products may cause damage or malfunction.

•  The control system is in conformity with the Low Voltage Directive and 

the EMC Directive for use in household, trade, industry and light industry.

•  When installed, the control system complies with protection degree  

IP 42.

•  The control system can operate smoke ventilation windows with a total 

power consumption of 10 A (KFC 210) and 2 x 10 A (KFC 220) respec-
tively.

•  The packaging must be disposed of in accordance with national regula-

tions.

• 

 Products, including batteries if any, marked with the crossed out 

wheeled bin are regarded as electrical and electronic equipment and 
contain hazardous materials, components and substances. The crossed 
out wheeled bin symbolises that electrical and electronic equipment 
waste must not be disposed of together with household waste. It must 
be collected separately at recycling stations or other collection sites or 
retrieved directly from households to increase the possibilities of recyc-
ling, reuse and utilisation of electrical and electronic equipment waste. 
By sorting electrical and electronic equipment waste with this symbol, 
you contribute to reducing the volume of incinerated or buried waste and 
to reducing any negative impact on human health and the environment. 
Further information can be obtained from the local municipality's techni-
cal administration or from your VELUX sales company.

•  If batteries can be removed, product and batteries must be disposed of 

separately.

Installation

•  Installation must be carried out by a certified person in accordance with 

current national regulations.

•  The control system must be connected directly to the mains supply in ac-

cordance with national regulations. Ensure that the mains supply cannot 
be disconnected unintentionally. It is recommended that disconnection 
is only possible using the mains switch or a key switch. At least one of 
these means for disconnection must be incorporated in the fixed wiring in 
accordance with national wiring requirements.

Maintenance and service

•  Disconnect mains supply and back-up batteries before carrying out any 

maintenance or service work to the control system and ensure that they 
cannot be reconnected unintentionally during this time.

•  The control system must be tested after installation, service work and 

alterations to the system. It must be inspected by qualified personnel at 
least once a year. Tests and inspections must be documented in accord-
ance with national regulations.

•  At the yearly inspection, the connected products must be checked ac-

cording to their instructions.

•  The printed circuit board monitors the time between inspection periods. 

If more than 15 months have passed since the last inspection, the yellow 
light-emitting diode is on and an acoustic alarm sounds.

•  The batteries must be checked at the yearly inspection. We recommend 

that the batteries are replaced at least every four years.

•  If you have any technical questions, please contact your VELUX sales 

company, see telephone list or www.velux.com.

Important information

Содержание KFX 210

Страница 1: ...KFC 210 220 For information on VELUX smoke ventilation please contact your VELUX sales company Tel 01592 778 225 UK Tel 01 848 8775 IE SMOKE VENTILATION 25 09 2014 07 44 14 Instructions for VELUX con...

Страница 2: ...2 VELUX...

Страница 3: ...rol unit 20 Back up batteries 21 Mains connection 22 Status and error indication in control system 23 25 Connected control units 26 31 Transmit alarm from one control unit KFC to another 26 Receive an...

Страница 4: ...the hazards involved Cleaning and user mainte nance must not be made by unsupervised chil dren Children must not play with the control system The installer must instruct the owner in the function of t...

Страница 5: ...m your VELUX sales company If batteries can be removed product and batteries must be disposed of separately Installation Installation must be carried out by a certified person in accordance with curre...

Страница 6: ...35 EU EMC Directive 2014 30 EU and the RoHS Directive 2011 65 EU have been manufactured in accordance with the harmonised standards EN 61000 3 2 2014 EN 61000 3 3 2013 EN 55014 1 2006 A1 2009 A2 2011...

Страница 7: ...VELUX 7...

Страница 8: ...n KFC 210 or KFC 220 see type designation in the control unit 2 Frame with instructions 3 Keys rubber bushes screws and cable ties 4 Labels 5 Back up batteries 6 Battery holder 7 Cables for batteries...

Страница 9: ...VELUX 9 1 ON 2 3 4 5 6 Keep the instructions behind the battery holder in the control unit Stick the supplied label SMOKE VENTILATION onto the indicated area on the control unit...

Страница 10: ...OTOR 1 230V 50Hz 24V H I M M 230 V 50 Hz B A C A Mains connection 19 B Motor 1 14 15 C Motor 2 14 15 D Smoke detector 11 E Rain sensor 12 F Ventilation switch 13 25 G Break glass point 10 H Alarm sign...

Страница 11: ...PSU1 OK OPERATION RESET SETUP RESET 73 C TEMP FUSE TIME AUTO CLOSE TIME OPENNIG COMFORT FRONT PANEL BREAK GLASS POINT RAIN RAIN IN COMFORT SMOKE RAIN OUT ERROR FUSE 25A 24V 1 ON 2 3 4 5 6 D E F G J K...

Страница 12: ...th a minimum cross section of 0 5 mm2 This cable can be up to 100 m long Break glass points KFK 100 101 102 103 104 must be installed in continuous single line con nections to ensure that the complete...

Страница 13: ...cordance with current national legislation After fitting the base the smoke detector can be snapped into place Position dust cover over the smoke detector until it is ready for operation Connection Th...

Страница 14: ...LARM FUSE 25A MOTOR 2 MOTOR 1 230V 50Hz 24V 24V 1 ON 2 3 4 5 6 3 2 1 RAIN The product can be purchased separately Note When fitting rain sensor KLA 200 use the instructions supplied with the sensor Co...

Страница 15: ...rately Connection The ventilation switch is connected to the control unit by means of a 3 core cable with a minimum cross section of 0 5 mm2 This cable can be up to 100 m long Output 1 Open Output 2 C...

Страница 16: ...1 Each terminal is intended for 24 V DC and max 10 A Control unit KFC 210 10 A In this example only motor terminal 1 is active Max 4 smoke ventilation windows GGL GGU K 40 or 1 smoke ventilation wind...

Страница 17: ...trol unit and motor and the prescribed cross sectional sizes of the cables are given in the table below The cable must be protected according to National European Standards Calculation of max cable le...

Страница 18: ...tches Cable errors are indicated by the yellow light emitting diode that flashes on and off and an acoustic alarm from control unit and connected break glass points Factory setting Remove thin foil be...

Страница 19: ...4 5 6 4 6 3 5 2 1 ON SE TUP 4 6 3 5 2 1 ON SE TUP 4 6 3 5 2 1 ON SE TUP 4 6 3 5 2 1 ON SE TUP 4 6 3 5 2 1 ON SE TUP 4 6 3 5 2 1 ON SE TUP Setting of switches Automatic time controlled closing of comf...

Страница 20: ...Green light emitting diode Under normal operation conditions the green light emitting diode in the control unit is on All other light emitting diodes are off If additional break glass points are conne...

Страница 21: ...hours in case of power failure Therefore if there is a fire alarm within these 72 hours the windows will still be able to open Note The batteries must be checked at the yearly inspection We recommend...

Страница 22: ...ME AUTO CLOSE TIME OPENNIG COMFORT FRONT PANEL BREAK GLASS POINT RAIN RAIN IN COMFORT SMOKE RAIN OUT ERROR ALARM FUSE 25A MOTOR 2 MOTOR 1 230V 50Hz 24V 24V 1 ON 2 3 4 5 6 PE N L 230V 50Hz 230 V Remove...

Страница 23: ...supply for motor terminal 2 used in control units KFC 220 only The light emitting diode indicates that the motor terminal is being supplied with power from the integrated power supply If the 230 V mai...

Страница 24: ...circuit board is on until the batteries are fully charged ERROR MOTOR 1 The printed circuit board monitors for defects in the cable from motor terminal 1 used in control units KFC 210 and KFC 220 If...

Страница 25: ...e middle and lowest pin to the top and middle pin see page 12 ERROR TEMP FUSE The printed circuit board monitors the temperature in the control unit If the temperature in the control unit rises above...

Страница 26: ...detectors and additional break glass points must be connected to control unit 1 only see below In the other control units the glass plate on the front face must be replaced by the blank lid provided...

Страница 27: ...IG COMFORT FRONT PANEL BREAK GLASS POINT RAIN RAIN IN COMFORT SMOKE RAIN OUT ERROR ALARM FUSE 25A MOTOR 2 MOTOR 1 230V 50Hz 24V 24V 1 ON 2 3 4 5 6 Receive and transmit error indications from one contr...

Страница 28: ...CLOSE TIME OPENNIG COMFORT FRONT PANEL BREAK GLASS POINT RAIN RAIN IN COMFORT SMOKE RAIN OUT ERROR ALARM FUSE 25A MOTOR 2 MOTOR 1 230V 50Hz 24V 24V 1 ON 2 3 4 5 6 3 2 1 COMFORT 3 2 1 COMFORT 3 2 1 CO...

Страница 29: ...RAIN OUT ERROR ALARM FUSE 25A MOTOR 2 MOTOR 1 230V 50Hz 24V 24V 1 ON 2 3 4 5 6 3 2 1 2 1 1 3 2 2 1 3 2 1 3 FACU RAIN RAIN IN SMOKE RAIN OUT ERROR Rain sensor The product can be purchased separately Co...

Страница 30: ...ontrol system according to the instructions supplied with them In this installation control unit KFC is controlled by the primary external control system and the smoke ventilation function will be act...

Страница 31: ...EAK GLASS POINT RAIN RAIN IN COMFORT SMOKE RAIN OUT ERROR ALARM FUSE 25A MOTOR 2 MOTOR 1 230V 50Hz 24V 24V 1 ON 2 3 4 5 6 1 3 2 ERROR a b Transmit alarms or error indications to other external equipme...

Страница 32: ...e control unit can be replaced by the coloured frame supplied applies to KFX 211 212 213 and 214 only Remove white frame as shown Place glass from the white frame in the coloured frame Fit the coloure...

Страница 33: ...hermo fuse 73 C Status LED in break glass point Green light system OK Yellow light error For details see page 15 and 18 20 Red light alarm active Environmental class 1 Operational temperature 5 C to 4...

Страница 34: ...34 VELUX...

Страница 35: ...VELUX 35...

Страница 36: ...Magyarorsz g Kft 06 1 436 0601 IE VELUX Company Ltd 01 848 8775 IT VELUX Italia s p a 045 6173666 JP VELUX Japan Ltd 0570 00 8141 KR VELUX International VELUX A S 45 7632 9240 LT VELUX Lietuva UAB 85...

Отзывы: