GLT-299-7-8 Rev. 0
Mar 23, 2018
6
4)
Short between terminal 1 and 5, and the yellow SCI indicator is illuminated. The short circuit isolator isolates
the devices connected after the short-circuited area, which makes these devices have no response. Upon
removal of the short condition, the area is automatically connected to go back to the normal operating status,
and the SCI indicator turns off.
Note
: For detector testing and cleaning information, refer to each detector's instruction manual as mentioned in
Section 4.
Section 8 – SPECIFICATIONS
SLC Applied Voltage
Rated Range 20VDC to 38VDC
SLC Current Consumption
Standby 100μA Activated(SCI Isolation) 22mA
SLC Line impedance
Up to 50ohms, 2km(1.24mile) (Refer to * below)
SCI On Resistance
0.2ohms (max)
SCI Fault Detection Voltage
10V (min)
Visual Indicator
(
Status LED
)
SCI
LED
(
yellow
)
UL Ambient Installation Temperature
0
℃
(32°F) to 3
8
℃
(100°F)
Operating Temperature
-10
℃(14°F)
to 55
℃
(131°F)
Storage Temperature
-20
℃
(-
4°F)
to 60
℃(140°F)
Max Relative Humidity
Up to 95
%
RH
,
non-condensing
Environment
Indoor dry use only
Terminal
Terminal for SLC: AWG12 to 20
Dimensions
φ105 mm x 22.5 mm H (φ4.133” x 0.885” H)
(Mount to a
3-1/2”
octagonal box
)
Weight
Approximately 79g (2.8 ounces)
Standard
UL268 and UL521
* Refer to the Installation and Operation Manual of Zeta Control Panel series to determine correct loop load and
maximum loop resistance for devices connected to each loop.