VELBUS INSTALLATION GUIDE
©2015 Velbus
66
www.velbus.eu
All modules with electronic addressing can use the full HEX range of 01-FE (in
decimal notation: 01
–
254).
In any case, check also if there are no wiring problems and restart the system
if necessary (power down, wait a few seconds and power up again).
In case of error, modules may have their LEDs blinking as follows:
blinking 2 x, pause, blinking 2 x, etc: communication error
blinking 3 x, pause, blinking 3 x, etc.: supply voltage too low
blinking 4 x, pause, blinking 4 x, etc.: supply voltage too high
This may vary between modules. Check the documentation of the specific
modules for further details.
An input module stops responding
Check if you haven’t programmed a delay in the button or input channel. Push
the button for at least three seconds to make sure.
The channel may also be locked. In Velbuslink, right click on the channel, select
“this module” > “unlock buttons”.
In case of a static electrical discharge, power down the system, wait a few
seconds and power up again.
A module with electronic addressing remains untraceable (red X next
to its state) in Velbuslink, although the LEDs on the module behave
normally
Check that you have not accidentally changed the address of this module? You
can find the module by opening the detection window in Velbuslink and
physically operate the module. You will see the module appear in Velbuslink
along with its correct address.
After a scan of my new modules I get continuous error messages if I try
to read or sync
All modules with electronic addressing have their address set to FF by factory
default. You must assign a new address to all modules before taking further