VELBUS INSTALLATION GUIDE
©2015 Velbus
58
www.velbus.eu
The actions to be created in Velbuslink are very straightforward. The glass
panels have special channels for heating (and cooling). In our example the
“pump” and “heater” channels intere
st us most. Whenever the measured
temperature drops below the target temperature (which depends on the
active mode: anti-freeze, day, night or comfort), these channels will be closed
(“Pressed”)
. Once the temperature is again equal to or higher than the target
temperature, the channels open again
(“Released”)
.
In the example below, the measured temperature is 22,5°C. As the target
temperature is set at 25°C, the heater and pump channels are closed
(“Pressed”).
Schematically represented, the actions to be created are the following (see
43 for more information on Velbus actions):