6 Setup

VEGATOR 636 Ex • Signal conditioning instrument

23446-EN-130627

A-mode

B-mode

2

 Simulation an empty signal (approx. 1.5

 

s)

Level relay energised

Relay control lamp lights

Relay control lamp off

2

 Simulation of an empty signal

Failure lamp

Failure lamp off

Failure lamp off

3

 Simulation of a full signal (approx. 1.5

 

s)

Level relay deenergised

Relay control lamp off

Relay control lamp lights

3

 Simulation of a full signal

Failure lamp

Failure lamp off

Failure lamp off

4

 Return to the current operating condition (covered/

uncovered)

Check the process of the function test. Take the following criteria into 

account for evaluation of the result:

Test passed

If all three switching conditions occur in the correct sequence and the 

specified duration (±20 %), then the test is passed and the instrument 

functions correctly.

Test not passed

 

The specified times deviate considerably from the table (>3 s)

 

One of the switching conditions remains unchanged

 

No start-up of the test - no signal sequence

6.3  Function chart

The following chart provides an overview of the switching conditions 

depending on the set mode and the level.
The mode switch on the sensor (if available) must be set to max. 

operation.

Sensor (max. opera-

tion)

Signal conditioning instrument

Mode on 

the signal 

condi-

tioning 

instrument

Level

Signal 

current - 

Sensor

Sig-

nal lamp 

- Switch-

ing output 

(yellow)

Con-

trol lamp 

- Failure 

(red)

Outputs

Mode A

Overflow 

protection

approx. 

mA

Relay ener

-

gized

transistor 

conducts

Mode A

Overflow 

protection

approx. 

16 

mA

Relay de

-

energized

transistor 

blocks

Evaluation

Содержание VEGATOR 636 Ex

Страница 1: ...Operating Instructions VEGATOR 636 Ex Signal conditioning instrument Ship approvals Document ID 23446...

Страница 2: ...duct description 3 1 Configuration 7 3 2 Principle of operation 8 3 3 Adjustment 8 3 4 Packaging transport and storage 8 4 Mounting 4 1 General instructions 10 4 2 Mounting instructions 10 5 Connectin...

Страница 3: ...ioning instrument 23446 EN 130627 Supplementary documentation Information Supplementary documents appropriate to the ordered version come with the delivery You can find them listed in chapter Product...

Страница 4: ...hese personnel and put into practice by them 1 3 Symbolism used Information tip note This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can...

Страница 5: ...explicitly forbidden 2 3 Warning about incorrect use Inappropriate or incorrect use of the instrument can give rise to application specific hazards e g vessel overfill or damage to system components t...

Страница 6: ...the Ex approved instruments 2 7 Environmental instructions Protection of the environment is one of our most important duties That is why we have introduced an environment management system with the g...

Страница 7: ...if necessary further certificates The VEGATOR 636 Ex consists of VEGATOR 636 Ex signal conditioning instrument 5 6 7 8 9 10 12 13 14 TEST on 3 1 2 Fig 1 VEGATOR 636 Ex 1 Ex separating chamber with Ex...

Страница 8: ...protected by packaging during transport Its capacity to handle normal loads during transport is assured by a test based on ISO 4180 The packaging of standard instruments consists of environment frien...

Страница 9: ...iption VEGATOR 636 Ex Signal conditioning instrument 23446 EN 130627 Storage and transport temperature see chapter Supplement Technical data Ambient conditions Relative humidity 20 85 Storage and tran...

Страница 10: ...cover IP 65 for surface mounting In this housing you can mount a maximum of 3 instruments of 36 mm width 4 2 Mounting instructions The plug in socket is constructed for carrier rail mounting according...

Страница 11: ...erminals according to the following illustration 1 2 4 3 Fig 3 Mounting the separating chamber All signal conditioning instruments are provided with different gaps dependent on type and version mechan...

Страница 12: ...Typ 600 1 5 6 7 8 14 13 12 10 9 4 3 2 1 EEx ia L1 N DISBUS 0 10V 9 8 7 3 2 1 C B A 12 Plug in socket 2 1 3 4 Fig 4 Plug in socket VEGATOR 636 Ex 1 Bridges for looping the operating voltage 2 Type cod...

Страница 13: ...round terminal The ground terminal on the outside of the sensor housing must be connected to the potential equalisation low impedance If potential equalisation currents are expected the connection on...

Страница 14: ...rsions make sure the Ex separating chamber is plugged above the sensor terminals The pins for type and Ex coding must also be inserted correctly 5 3 Wiring plan 3 5 4 1 2 5 6 7 8 1 2 3 4 9 10 12 13 14...

Страница 15: ...T EEx ia L1 N DISBUS 0 10V 9 8 7 3 2 1 C B A 12 Plug in socket 6 5 10 7 7 8 9 1 2 3 4 Fig 6 Display and adjustment elements 1 Test key 2 Control lamp level relay LED yellow 3 Control lamp Fault signal...

Страница 16: ...54W max 250VAC DC 9 10 Uo xx V Lo xx mH Co xx nF Po xx mW Io xx mA 1 2 3 Fig 7 Display and adjustment elements 1 DIL switch block 2 Type plate 3 Transparent cover 6 2 Adjustment elements Control lamps...

Страница 17: ...on delays independent of each other The delay refers to the switching function of the relay In the example see previous illustration mode A max detection of overfill protection is selected switch 1 T...

Страница 18: ...pushing the key the system is checked on the following criteria Switching function of the switching outputs Potential separation of the outputs The signal processing of the signal conditioning instru...

Страница 19: ...tching conditions occur in the correct sequence and the specified duration 20 then the test is passed and the instrument functions correctly Test not passed The specified times deviate considerably fr...

Страница 20: ...tioning instrument Level Signal current Sensor Sig nal lamp Switch ing output yellow Con trol lamp Failure red Outputs Mode B Dry run protection approx 16 mA Relay ener gized transistor conducts Mode...

Страница 21: ...49 1805 858550 The hotline is available to you 7 days a week round the clock Since we offer this service world wide the support is only available in the English language The service is free of charge...

Страница 22: ...ld the failure lamp extinguish the sensor will be defective Exchange the sensor or send it in for repair The red failure control lamp LED of the signal conditioning instrument lights Current value 23...

Страница 23: ...Internet homepage www vega com under Downloads Forms and certificates Repair form By doing this you help us carry out the repair quickly and without hav ing to call back for needed information Print a...

Страница 24: ...ly separable WEEE directive 2002 96 EG This instrument is not subject to the WEEE directive 2002 96 EG and the respective national laws Pass the instrument directly on to a spe cialised recycling comp...

Страница 25: ...t circuit proof Sensor operating voltage 15 18 V DC Detection line break 2 3 mA Detection shortcircuit 23 2 mA Configuration connection cable 2 wire Resistance per conductor max 35 Relay output Number...

Страница 26: ...n class II Electrical separating measures reliable separation VDE 0106 part 1 between power supply sensor input level relay and transistor output Functional safety SIL The instrument can be used in sa...

Страница 27: ...trument 23446 EN 130627 9 2 Dimensions 118 5 mm 4 67 134 mm 5 28 36 mm 1 42 54 5 mm 2 15 5 6 7 8 9 10 12 13 14 1 2 on 3 Fig 23 Dimensions VEGATOR 636 Ex 1 Transparent cover 2 Carrier rail 35 x 7 5 or...

Страница 28: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: