6.1 General information
The figures in brackets refer to the following illustrations.
In the basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³)
can be detected. For products with lower density, you have to set the
switch to ≥ 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
•
Signal lamps (1, 2, 3)
•
DIL switch for mode adjustment - min./max. (4)
•
DIL switch for sensitivity adjustment (5)
Note:
For test purposes, immerse the tuning fork of VEGASWING 66 always
in liquids. Do not test the function of VEGASWING 66 with your hand.
This can damage the sensor.