7 Maintenance and fault rectification
VEGASWING 63 • Two-wire 8/16 mA
29232-EN-180704
Error
Cause
Rectification
Control lamp off
Error on the vibrating el-
ement
Check if the vibrating element is damaged or extreme-
ly corroded.
Interference on the elec-
tronics module
Exchanging the electronics module
instrument defective
Exchange the instrument or send it in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Set up
" may have to be carried out again.
7.3 Exchanging the electronics
If the electronics module is defective, it can be replaced by the user.
In Ex applications only an electronics module with respective Ex ap-
proval may be used.
You can find all the information you need to carry out an electronics
exchange in the handbook of the new electronics module.
In general, all electronics modules of series SW60 can be inter-
changed. If you want to use an electronics module with a different
signal output, you carry out the complete setup. You find the neces-
sary, suitable operating instruction on our homepage.
Note:
Keep in mind that enamelled instrument versions need special
electronics modules. These electronics modules are called SW60E or
SW60E1.
7.4 How to proceed if a repair is necessary
You can find an instrument return form as well as detailed informa-
tion about the procedure in the download area of our homepage:
www.vega.com.
By doing this you help us carry out the repair quickly and without hav-
ing to call back for needed information.
If a repair is necessary, please proceed as follows:
•
Print and fill out one form per instrument
•
Clean the instrument and pack it damage-proof
•
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
•
Please contact the agency serving you to get the address for
the return shipment. You can find the agency on our home page
www.vega.com.
Reaction after fault recti-
fication