70
11 Supplement
VEGAPULS SR 68 • 4 … 20 mA/HART two-wire
38294-EN-130624
3
4
2
1
Fig. 55: Data of the input variable
1 Reference plane
2 Measured variable, max. measuring range
3 Antenna length
4 Useful measuring range
Max. measuring range
30 m (98.43 ft)
Recommended meas. range depending on the antenna diameter
Ʋ ø 40 mm (1.575 in)
up to 15 m (49.21 ft)
Ʋ ø 48 mm (1.89 in)
up to 20 m (65.62 ft)
Ʋ ø 75 mm (2.953 in), 95 mm (3.74 in)
up to 30 m (98.43 ft)
Ʋ Parabolic antenna
up to 30 m (98.43 ft)
Output variable
Output signal
4 … 20 mA/HART
Range of the output signal
3.8 … 20.5 mA/HART (default setting)
Fulfilled HART specification
7.0
Signal resolution
0.3 µA
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current
22 mA
Starting current
≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on
Load
see load diagram under Power supply
Damping (63 % of the input variable),
adjustable
0 … 999 s