5 Mounting
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66190-EN-221107
r
r
r...
/
1 3
/
1 2
Fig. 33: Mounting position and orientation
Direct the device in such a way that the radar signal reaches the
lowest vessel level. Hence it is possible to detect the complete vessel
volume.
Tip:
The easiest way to align the device is with the optional swivelling
holder. Determine the suitable inclination angle and check the align-
ment with the alignment aid in the VEGA Tools app on the device.
Alternatively, the angle of inclination can be determined using the
following drawing and table. It depends on the measuring distance "d"
and the distance "a" between vessel centre and mounting position.
Check the alignment with a suitable level or water level.