The VEGAPULS 6X must be connected via suitable cable gland or conduit systems that are in
conformity with the requirements of the standards and provided with a separate type approval
certificate. When connecting the VEGAPULS 6X to conduit systems, the corresponding sealing
facility must be connected directly to the housing. Keep the type and size of the threads in mind:
The thread names are mentioned on the type label
•
Unused openings must be covered according to the standards. The red thread or/dust covers
screwed in when the instruments are shipped (depending on the version) must be removed
before setup and replaced by cable entries or closing screws suitable for the respective ignition
protection type and IP protection.
•
The connection cable of VEGAPULS 6X has to be wired fix and in such a way that damages can
be excluded
•
Lids must not be opened if there is a hazardous atmosphere. The housing lids are marked with
the warning label:
WARNING - DO NOT OPEN WHEN AN
EXPLOSIVE ATMOSPHERE IS PRESENT
7
Electrostatic charging (ESD)
In case of instrument versions with electrostatically chargeable plastic parts, the danger of electro-
static charging and discharging must be taken into account!
The following parts can charge and discharge:
•
Lacquered housing version or alternative special lacquering
•
Plastic housing, plastic housing parts
•
Plastic process fittings
•
Plastic-coated process fittings and/or plastic-coated sensors
•
Connection cable for separate versions
•
Type label
Take note in case of danger of electrostatic charges:
•
Avoid friction on the surfaces
•
Do not dry clean the surfaces
The instruments must be installed in such a way that the following can be ruled out:
•
electrostatic charges during operation, maintenance and cleaning.
•
process-related electrostatic charges, e.g. by measuring media flowing past
The warning label indicates danger:
WARNING - POTENTIAL ELECTROSTATIC
CHARGING HAZARD - SEE INSTRUCTIONS
8
Electrical data
For the VEGAPULS 6X in ignition protection type dust ignition protection by enclosure (IIIC) applies:
Power supply and signal circuit: terminals 1[+], 2[-]
The following values must be observed or taken into account:
Supply via a circuit with limited power (max. 100 W, see operating instructions), e.g. a class 2 power
supply unit common in North America
•
U = 12 … 35 V DC