57
6 Set up with the display and adjustment module
VEGAPULS 68 • Foundation Fieldbus
36538-EN-170405
•
Setup:
Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
•
False signal suppression:
Deletes a previously created false
signal suppression. The false signal suppression created at the
factory remains active.
•
Peak values, measured value:
Resets the measured min. and
max. distances to the current measured value.
Select the requested reset function
[->]
and confirm with
[OK]
.
The following table shows the default values of VEGAPULS 68:
Menu section
Menu item
Default value
Setup
Measurement loop name
Sensor
Medium
Liquid/Water
Bulk solids/Crushed stones, gravel
Application
Storage tank
Silo
Vessel form
Vessel bottom, dished form
Vessel top, dished form
Vessel height/Measur-
ing range
Recommended measuring range, see "
Technical data
"
in the supplement
Min. adjustment
Recommended measuring range, see "
Technical data
"
in the supplement
Damping
0.0 s
Display
Language
Like order
Displayed value
Distance
Display unit
m(d)
Scaling
0.00 %, 0 l
100.00 %, 100 l
Backlight
Switched on
Additional settings
Distance unit
m
Temperature unit
°C
Unit SV2
m
Probe length
Length of standpipe ex factory
Linearisation curve
Linear
The instrument settings are copied with this function. The following
functions are available:
•
Store data from sensor in the display and adjustment module.
•
Store data from display and adjustment module in the sensor
Additional settings - Copy
instrument settings