6 Set up with the display and adjustment module PLICSCOM
VEGAPULS 66 • 4 … 20 mA/HART - two-wire
28438-EN-170927
– Move to the menu overview
– Confirm selected menu
– Edit parameter
– Save value
•
[->]
key to select:
– Menu change
– Select list entry
– Select editing position
•
[+]
key:
– Change value of the parameter
•
[ESC]
key:
– Interrupt input
– Jump to next higher menu
The instrument is operated via the four keys of the display and adjust-
ment module. The individual menu items are shown on the LC display.
You can find the functions of the individual keys in the previous
illustration.
When the
[+]
and
[->]
keys are pressed quickly, the edited value,
or the cursor, changes one value or position at a time. If the key is
pressed longer than 1 s, the value or position changes continuously.
When the
[OK]
and
[ESC]
keys are pressed simultaneously for more
than 5 s, the display returns to the main menu. The menu language is
then switched over to "
English
".
Approx. 60 minutes after the last pressing of a key, an automatic reset
to measured value indication is triggered. Any values not confirmed
with
[OK]
will not be saved.
6.4 Setup steps
In HART-Multidrop mode (several sensors on one input) the address
must be set before continuing with the parameter adjustment. You
will find a detailed description in the operating instructions manual
"
Display and adjustment module
" or in the online help of PACTware
or DTM.
HART mode
Standard
Address 0
The radar sensor measures the distance from the sensor to the
product surface. For indication of the real level, an allocation of the
measured distance to the percentage height must be carried out.
Adjustment system
Time functions
Address setting HART
multidrop
Parameterization example