15
5 Set up with the display and adjustment module
VEGAPULS 64 • 4 … 20 mA/HART - two-wire
51462-EN-160111
The return to the measured value indication is carried out through the
[->]
or
[ESC]
keys or automatically after 3 s
The menu "
Extended adjustment
" is available for further settings. Im-
portant functions are described in the following chapter. You can find a
complete description of all functions of the "
Extended adjustment
" in
the operating instructions manual of VEGAPULS 64.
5.3 Parameter adjustment - Extended adjustment
The main menu is divided into five sections with the following func-
tions:
Setup: Settings, e.g., for measurement loop name, units, application,
adjustment, signal output
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, for example, on device status, peak value,
simulation, echo curve
Additional adjustments: Date/Time, reset, copy function, scaling,
current output, false signal suppression, linearization, HART mode,
special parameters
Info: Instrument name, hardware and software version, calibration
date, instrument features
In the main menu item "
Setup
", the individual submenu items
should be selected one after the other and provided with the correct
parameters to ensure optimum adjustment of the measurement. The
procedure is described in the following.
Since the radar sensor is a distance measuring instrument, the
distance from the sensor to the product surface is measured. To
indicate the actual level, an allocation of the measured distance to the
percentage height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
Extended adjustment
Main menu
Setup - Adjustment