0 %
100 %
1
2
5
4
3
6
F
ig
.
14
:
C
on
fi
guration bypass
1
R
adar sensor
2
M
arking of the polarisation plane
3
I
nstrument
fl
ange
4
D
istance sensor reference plane to upper tube connection
5
D
istance of the tube connections
6
B
all valve with complete opening
I
nstructions for orientation
:
l
N
ote marking of the polarisation plane on the sensor
l
W
ith threaded
fi
tting
,
the marking is on the hexagon
,
with
fl
ange
connection between the two
fl
ange holes
l
T
he marking must show to the direction of the tube connections to
the vessel
I
nstructions for the measurement
:
l
T
he
100
%
point must not be above the upper tube connection to
the vessel
l
T
he
0
%
point must not be below the lower tube connection to the
vessel
l
M
in
.
distance sensor reference plane to the upper edge upper
tube connection
>
300
mm
l
F
or the parameter adjustment
,
select
"
A
pplication standpipe
"
and
enter the tube diameter to compensate errors due to running time
shift
l
A
false signal suppression with integrated sensor is recommended
but not mandatory
l
T
he measurement through a ball valve with complete run is
possible
C
onstructional requirements on the bypass pipe
:
VEGAPULS
62
•
4
…
20
m
A
/
HART
two
-
wire
21
4
M
ounting
36503
-
EN
-
100607