0%
100%
1
2
3
1
2
3
4
5
8
6
7
9
F
ig
.
13
:
C
on
fi
guration surge pipe
1
R
adar sensor
2
M
arking of the polarisation plane
3
T
hread or
fl
ange on the instrument
4
V
ent hole
5
H
oles
6
W
eld joint
7
W
elding neck
fl
ange
8
B
all valve with complete opening
9
F
astening of the surge pipe
I
nstructions for orientation
:
l
N
ote marking of the polarisation plane on the sensor
l
W
ith threaded
fi
tting
,
the marking is on the hexagon
,
with
fl
ange
connection between the two
fl
ange holes
l
T
he marking must show to the direction of the holes in the surge
pipe
I
nstructions for the measurement
:
l
T
he
100
%
point must be below the upper vent hole and the
antenna edge
l
T
he
0
%
point is the end of the surge pipe
l
F
or the parameter adjustment
,
select
"
A
pplication standpipe
"
and
enter the tube diameter to compensate errors due to running time
shift
l
A
false signal suppression with integrated sensor is recommended
but not mandatory
VEGAPULS
62
•
4
…
20
m
A
/
HART
two
-
wire
19
4
M
ounting
36503
-
EN
-
100607