C
aution
:
N
ote the following if the instrument with corresponding approval is
used as part of an over
fi
ll protection system according to
WHG
:
I
f a linearisation curve is selected
,
the measuring signal is no longer
compulsorily linear proportional to the level
.
T
his must be taken into
consideration by the user
,
particularly when adjusting the switching
point on the level switch
.
W
ith radar sensors with standpipe antenna
,
the sensor length is
already preset in this menu item
.
W
hen shortening the standpipe
antenna afterwards
,
this value must be corrected respectively
.
W
hen a reset is carried out
,
all settings
(
with only a few exceptions
)
are
reset
.
T
he exceptions are
:
PIN
,
language and lighting
.
T
he following reset functions are available
:
D
elivery status
:
R
estoring the parameter settings at the time of
shipment from the factory incl
.
the order
-
speci
fi
c settings
.
A
created
false signal suppression
,
user
-
programmable linearization curve as
well as the measured value memory will be deleted
.
B
asic settings
:
R
esetting the parameter settings incl
.
special and
laboratory parameters to the default values of the respective instru
-
ment
.
A
created false signal suppression
,
user programmable
linearization curve as well as the measured value memory will be
deleted
.
S
etup
:
R
esetting of the parameter settings to the default values of the
respective instrument in the menu item
S
etup
.
O
rder
-
related settings
remain but are not taken over into the current parameters
.
U
ser
-
generated false signal suppression
,
user
-
programmed linearization
curve
,
measured value memory as well as event memory remain
untouched
.
T
he linearization is set to linear
.
F
alse signal suppression
:
D
eleting a previously created false signal
suppression
.
T
he false signal suppression created in the factory
remains active
.
P
eak values distance
:
R
esetting the measured min
.
and max
.
distances to the actual measured value
.
S
elect the requested reset function
[-
>
]
and con
fi
rm with
[
OK
]
.
A
dditonal settings
/
P
ro
-
be length
A
dditional settings
/
R
e
-
set
VEGAPULS
62
standpipe version
•
F
oundation
F
ieldbus
29
6
S
et up with the indicating and adjustment module
36510
-
EN
-
120301
Содержание VEGAPULS 62 standpipeversion
Страница 1: ...Operating Instructions VEGAPULS 62 standpipe version Foundation Fieldbus Document ID 36510 Radar...
Страница 73: ...VEGAPULS 62 standpipe version Foundation Fieldbus 73 Index 36510 EN 120301...
Страница 74: ...74 VEGAPULS 62 standpipe version Foundation Fieldbus Index 36510 EN 120301...
Страница 75: ...VEGAPULS 62 standpipe version Foundation Fieldbus 75 Index 36510 EN 120301...