background image

1

.

4

S

etup

T

ake note of the mounting and installation instructions of the

operating instructions manual

.

I

n the setup procedure

,

a check of the safety function by

means of an initial

lling is recommended

.

1

.

5

R

eaction during operation and in case of

failure

T

he adjustment elements or device parameters must not be

modi

ed during operation

.

I

f modi

cations have to be made during operation

,

carefully

observe the safety functions

.

F

ault signals that may appear are described in the appropriate

operating instructions manual

.

I

f faults or error messages are detected

,

the entire measuring

system must be shut down and the process held in a safe state
by other measures

.

A

n exchange of the electronics is easily possible and is

described in the operating instructions manual

.

I

f due to a detected failure the electronics or the complete

sensor is exchanged

,

the manufacturer must be informed

(

incl

.

a fault description

).

1

.

6

R

ecurring function test

T

he recurring function test is used to check the safety function

,

to detect possible non

-

detectable dangerous faults

.

T

he

function of the measuring system must be checked in
adequate intervals

.

T

he operator is responsible for choosing the type of check

.

T

he time intervals depend on the selected

PFD

avg

value

according to chart and diagram in paragraph

"

S

afety

-

related

characteristics

"

.

W

ith high demand rate

,

a recurring function test is not

requested in

IEC

61508

.

T

he function of the measuring system

is demonstrated by the frequent use of the system

.

I

n double

channel architectures it is a good idea to verify the redundancy
through recurring function tests at appropriate intervals

.

M

ounting and installation

I

n general

VEGAPULS

series

60

-

4

20

m

A

/

HART

9

F

unctional safety

31338

-

EN

-

070510

Содержание VEGAPULS 61

Страница 1: ...Safety Manual VEGAPULS series 60 4 20 mA HART Radar...

Страница 2: ...1 2 Planning 5 1 3 Instrument parameter adjustment 7 1 4 Setup 9 1 5 Reaction during operation and in case of failure 9 1 6 Recurring function test 9 1 7 Safety related characteristics 10 2 VEGAPULS s...

Страница 3: ...le up to SIL2 in a single channel architecture 1oo1D and up to SIL3 in a multiple channel diverse redundant architecture The use of the measuring system in a multiple channel homogeneous redundant arc...

Страница 4: ...for the process industry sector Part 1 Framework de ni tions system hardware and software requirements Failure limit values for a safety function depending on the SIL class of IEC 61508 1 7 6 2 Safety...

Страница 5: ...signal is transmitted to a connected processing unit to monitor the following conditions l Exceeding a preset level l Falling below a preset level When the switching point set on the processing unit i...

Страница 6: ...3 5 12 If the ratio of the internal diagnostics test rate of the measuring system to the demand rate exceeds the value 100 the measuring system can be treated as if it is executing a safety function i...

Страница 7: ...t used for transmission of safety relevant information The measuring system should be used appropriately taking pressure temperature density dielectric value and chemical properties of the medium into...

Страница 8: ...fter connecting the instrument the output signal jumps to the set interference current at the end of the switch on phase l In mode Simulation the signal current can be simulated independent of the act...

Страница 9: ...anual If due to a detected failure the electronics or the complete sensor is exchanged the manufacturer must be informed incl a fault description 1 6 Recurring function test The recurring function tes...

Страница 10: ...7 Safety related characteristics The failure rates of the electronics the mechanical parts of the transmitter as well as the process tting are determined by an FMEDA according to IEC 61508 The calcula...

Страница 11: ...executable sensor software 15 h VEGAPULS 68 and VEGAPULS 61 62 63 with increased sensitivity E013 no measured value available 2 36 min depending on the application E042 E043 hardware error 4 min E036...

Страница 12: ...5 years 4 PFDavg after 10 years Multiple channel architecture If the measuring system is used in a multiple channel architecture the safety relevant characteristics of the selected structure of the m...

Страница 13: ...VEGAPULS series 60 4 20 mA HART 13 Functional safety 31338 EN 070510...

Страница 14: ...14 VEGAPULS series 60 4 20 mA HART Functional safety 31338 EN 070510...

Страница 15: ...VEGAPULS series 60 4 20 mA HART 15 Functional safety 31338 EN 070510...

Страница 16: ...om www vega com ISO 9001 All statements concerning scope of delivery application practical use and operating conditions of the sensors and processing systems correspond to the information avail able a...

Отзывы: