G
ating out of false signals
C
hange now
?
P
roceed as follows
:
1
M
ove from the measured value display to the main menu by
pushing
[
OK
]
.
2
S
elect the menu item
"
S
ervice
"
with
[-
>
]
and con
fi
rm with
[
OK
]
.
N
ow the menu item
"
F
alse signal suppression
"
is displayed
.
3
C
on
fi
rm
"
F
alse signal suppression
-
C
hange now
"
with
[
OK
]
and
select in the below menu
"
C
reate new
"
.
E
nter the actual distance
from the sensor to the product surface
.
A
ll false signals in this area
are detected by the sensor and saved after con
fi
rming with
[
OK
]
.
N
ote
:
C
heck the distance to the product surface
,
because if an incorrect
(
too
large
)
value is entered
,
the existing level will be saved as false signal
.
T
he
fi
lling level would then no longer be detectable in this area
.
T
his function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module
.
A
description of the function is available in the
operating instructions manual
"
I
ndicating and adjustment module
"
.
T
he following data are read out or written with this function
:
l
M
easured value presentation
l
A
djustment
l
M
edium
l
V
essel form
l
D
amping
l
L
inearisation curve
l
S
ensor
-
TAG
l
D
isplayed value
l
D
isplay unit
l
S
caling
l
C
urrent output
l
U
nit of measurement
l
L
anguage
l
S
ensitivity
T
he following safety
-
relevant data are
not
read out or written
:
l
HART
mode
l
PIN
l
SIL
l
S
ensor length
/
S
ensor type
l
G
ating out of false signals
C
opy sensor data
VEGAFLEX
62
•
4
…
20
m
A
/
HART
two
-
wire
35
6
S
et up with the indicating and adjustment module
PLICSCOM
31837
-
EN
-
090831