K
eep in mind that interfaces can cause faulty measurements
.
I
f you want to measure the total height of both liquids reliably
,
please
contact our service department or use an instrument specially
designed for interface measurement
.
S
tart your parameter adjustment with the following menu items of the
basic adjustment
:
P
roceed as follows
:
1
M
ove from the measured value display to the main menu by
pushing
[
OK
]
.
▶
B
asic adjustment
D
isplay
D
iagnostics
S
ervice
I
nfo
2
S
elect the menu item
"
B
asic adjustment
"
with
[-
>
]
and con
fi
rm with
[
OK
]
.
N
ow the menu item
"
M
in
.
adjustment
"
is displayed
.
M
in
.
adjustment
0
.
00
%
=
10
.
000
m
(
d
)
8
.
000
m
(
d
)
3
P
repare the
%
value for editing with
[
OK
]
and set the cursor to the
requested position with
[-
>
]
.
S
et the requested percentage value
with
[
+
]
and save with
[
OK
]
.
T
he cursor jumps now to the distance
value
.
4
E
nter the suitable distance value in m for the empty vessel
(
e
.
g
.
distance from the sensor to the vessel bottom
)
corresponding to
the percentage value
.
5
S
ave the settings with
[
OK
]
and move to
"
M
ax
.
adjustment
"
with
[-
>
]
.
P
roceed as follows
:
M
ax
.
adjustment
100
.
00
%
=
1
.
000
m
(
d
)
2
.
000
m
(
d
)
1
P
repare the
%
value for editing with
[
OK
]
and set the cursor to the
requested position with
[-
>
]
.
S
et the requested percentage value
with
[
+
]
and save with
[
OK
]
.
T
he cursor jumps now to the distance
value
.
C
arrying out min
.
ad
-
justment
C
arrying out max
.
ad
-
justment
32
VEGAFLEX
62
•
4
…
20
m
A
/
HART
two
-
wire
6
S
et up with the indicating and adjustment module
PLICSCOM
31837
-