4 Mounting
VEGACAP 65 • Two-wire
30019-EN-230510
The probe must be mounted in a way that takes the arrangement of
the filling and emptying apertures into account.
To compensate measurement errors caused by the material cone in
cylindrical vessels, the sensor must be mounted at a distance of d/6
from the vessel wall.
d
d
d
6
d
6
Fig. 6: Filling and emptying centred