7 Diagnostics and servicing
VEGACAP 35 • Relay (DPDT)
33759-EN-230510
7. Open the tensile ring on the old electronics module and pull out
the old electronics module.
8. Compare the new electronics module with the old one. The type
label of the electronics module must correspond to that of the old
electronics module.
9. Insert the new electronics module.
10. Screw in and tighten the two screws with a Torx screwdriver.
11. Lead the connection cable through the cable gland.
12. Insert the wire ends into the open terminals according to the wir-
ing plan and tighten them.
13. Check the hold of the wires in the terminals by lightly pulling on
them.
14. Tighten cable gland and check on tightness. The seal ring must
completely encircle the cable.
15. Carry out a fresh adjustment. See chapter "
Set up, new adjust-
ment
".
16. Screw the housing lid back on
The electronics exchange is now finished.
7.4 Shortening of the probe
The cable of the probe can be shortened individually.