5 Connecting to power supply
VEGACAP 35 • Relay (DPDT)
33759-EN-230510
2
3 4 5 6 7
+
L1
–
N
8
1
1
2
3
Fig. 7: Wiring plan
1 Relay output
2 Relay output
3 Voltage supply
If inductive loads or stronger currents are switched through, the gold
plating on the relay contact surface will be permanently damaged.
The contact is then no longer suitable for switching low-voltage
circuits.
Inductive loads also result from the connection to a PLC input or
output and/or in combination with long cables. It is imperative that you
take measures to extinguish sparks to protect the relay contact (e.g. Z
diode) or use an electronic version with transistor output.
Connection to a PLC