7 Diagnostics and servicing
VEGACAP 35 • Relay (DPDT)
33759-EN-230510
Error
Cause
Rectification
•
The instrument signals
covered without being
covered by the medium
•
The instrument signals
uncovered while covered
with the medium
Wrong mode selected
Set the correct mode on the mode switch (A - overflow
protection, B - dry run protection). Wiring should be car-
ried out according to the idle current principle.
Operating voltage too low Check operating voltage
Shortcircuit in the probe,
e.g. because of moisture in
the housing
Remove the electronics module. Check the resistance
between the marked plug connections. See the follow-
ing instructions.
Electronics defective
Press the mode switch (A/B). If the instrument then
changes the mode, the instrument may be mechani-
cally damaged. Should the switching function in the
correct mode still be faulty, return the probe for repair.
Push the mode switch. If the probe then does not
change the mode, the electronics module may be de-
fective. Exchange the electronics module.
Remove the electronics module. Check the resistance between the
two plug connections.
There must no longer be a connection (high impedance). If there is
still a connection, exchange the instrument or return it for repair
Checking the switching
signal
Check the resistance in
the probe