M
easured value on the indicating and adjustment module does not
correspond to the value in the
PLC
l
T
he menu item
"
D
isplay
-
D
isplay value
"
is not set to
"
PA
-
O
ut
"
à
C
heck values and correct
,
if necessary
?
N
o connection between
PLC
and
PA
network
l
I
ncorrect adjustment of the bus parameter and the segment
coupler
-
dependent baud rate
à
C
heck data and correct
,
if necessary
?
I
nstrument does not appear during connection setup
l
P
ro
fi
bus
DP
cable pole
-
reversed
à
C
heck cable and correct
,
if necessary
l
I
ncorrect termination
à
C
heck termination at the beginning and end points of the bus
and terminate
,
if necessary
,
according to the speci
fi
cation
l
I
nstrument not connected to the segment
,
double assignment
of an address
à
C
heck and correct
,
if necessary
I
n
E
x applications
,
the regulations for the wiring of intrinsically safe
circuits must be observed
.
?
E
013
l
no measured value available
à
S
hort
-
circuit due to bridging by conductive buildup between
process
fi
tting and electrode
à
R
emove buildup
-
if necessary
,
mount a protective tube
l
S
hortcircuit in the probe
,
e
.
g
.
because of moisture in the
housing
à
R
emove the electronics module and check the resistance
between the marked plug connections according to the
following illustration
.
F
ault messages via the
indicating
/
adjustment
module
38
VEGACAL
62
•
P
ro
fi
bus
PA
8
M
aintenance and fault recti
fi
cation
30025
-
EN
-
090603
Содержание VEGACAL 62
Страница 1: ...Operating Instructions VEGACAL 62 Pro bus PA Document ID 30025 Capacitive...
Страница 14: ...Fig 5 In owing medium 14 VEGACAL 62 Pro bus PA 4 Mounting 30025 EN 090603...
Страница 57: ...VEGACAL 62 Pro bus PA 57 10 Supplement 30025 EN 090603...
Страница 58: ...58 VEGACAL 62 Pro bus PA 10 Supplement 30025 EN 090603...
Страница 59: ...VEGACAL 62 Pro bus PA 59 10 Supplement 30025 EN 090603...