10
.
2
I
nformation on
P
ro
fi
bus
PA
I
nstrument master
fi
le
T
he instrument master
fi
le
(
GSD
)
contains the characteristic data of the
P
ro
fi
bus
PA
instrument
.
T
hese data are
,
e
.
g
.
the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the
PA
instrument
.
A
bitmap
fi
le is also provided for the
P
ro
fi
bus network planning tool
.
T
his
fi
le is installed automatically
when the
GSD
fi
le is integrated
.
T
he bitmap
fi
le is used for symbolic indication of the
PA
instrument in
the con
fi
guration tool
.
I
dent number
E
ach
P
ro
fi
bus instrument gets an unambiguous ident number
(
ID
number
)
from the
P
ro
fi
bus user
organisation
(
PNO
).
T
his
ID
number is also included in the name of the
GSD
fi
le
.
F
or
VEGABAR
65
the
ID
number is
0
x
076
F
(
hex
)
and the
GSD
fi
le
BR
__
076
F
.
GSD
.
A
s an option to this manufacturer
-
speci
fi
c
GSD
fi
le
,
PNO
provides also a general so
-
called pro
fi
le
-
speci
fi
c
GSD
fi
le
.
F
or
VEGABAR
65
you have to use the general
GSD
fi
le
PA
139701
.
GSD
.
I
f the general
GSD
fi
le is used
,
the sensor
must be set to the pro
fi
le
-
speci
fi
c ident number via the
DTM
software
.
B
y default
,
the sensor operates
with the manufacturer
-
speci
fi
c
ID
number
.
N
ote
:
W
hen using the pro
fi
le
-
speci
fi
c
GSD
fi
le
,
the
PA
-
OUT
value as well as
the temperature value are transmitted to the
PLC
(
see block diagram
"
C
yclical data tra
ffi
c
"
).
C
yclical data tra
ffi
c
T
he master class
1
(
e
.
g
.
PLC
)
cyclically reads out measured values from the sensor during operation
.
T
he below block diagram below shows which data can be accessed by the
PLC
.
VEGABAR
65
•
P
ro
fi
bus
PA
61
10
S
upplement
28253
-
EN
-
081209