I
nformation
:
F
or an adjustment with
fi
lling
,
you simply enter the displayed actual
measured value
.
I
f the adjustment ranges are exceeded
,
the message
"
O
utside parameter limits
"
appears
.
T
he editing procedure can be
aborted with
[
ESC
]
or the displayed limit value can be accepted with
[
OK
]
.
P
roceed as follows
:
1
E
dit the
%
value in the menu item
"
M
ax
.
adjustment
"
with
[
OK
]
.
M
ax
.
adjustment
+
100
.
0
%
=
+
1000
.
0
mbar
0000
.
0
mbar
I
nformation
:
T
he displayed pressure for
100
%
corresponds to the nominal
measuring range of the sensor
(
in the above example
1
bar
=
1000
mbar
).
2
S
et the requested percentage value with
[-
>
]
and
[
OK
]
.
3
E
dit the requested mbar value with
[
OK
]
.
4
S
et the requested mbar value with
[
+
]
and
[-
>
]
.
5
C
on
fi
rm with
[
OK
]
and move to the menu overview with
[
ESC
]
.
T
he max
.
adjustment is
fi
nished
.
I
nformation
:
F
or an adjustment with
fi
lling
,
you simply enter the displayed actual
measured value
.
I
f the adjustment ranges are exceeded
,
the message
"
O
utside parameter limits
"
appears
.
T
he editing procedure can be
aborted with
[
ESC
]
or the displayed limit value can be accepted with
[
OK
]
.
P
rocess pressure measurement
S
et up
VEGABAR
65
in the following sequence
:
1
S
elect application
"
P
rocess pressure measurement
"
2
S
elect the unit of measurement
3
C
arry out position correction
4
C
arrying out zero adjustment
5
C
arrying out span adjustment
I
n the menu item
"
A
djustment unit
"
you select the physical unit in which
the adjustment should be carried out
,
e
.
g
.
mbar
,
bar
,
psi
…
T
he position correction compensates the in
fl
uence of the mounting
position or static pressure on the measurement
.
I
t does not in
fl
uence
the adjustment values
.
C
arrying out max
.
ad
-
justment
P
arameter ad
-
justment
"
P
roc
-
ess pressure
measurement
"
VEGABAR
65
•
P
ro
fi
bus
PA
35
6
S
et up with the indicating and adjustment module
PLICSCOM
28253
-
EN
-
081209