59
10 Supplement
VEGAPULS 61 • Profibus PA
28444-EN-141215
Status
code
Description according to
Profibus standard
Possible cause
0 x 0C
bad - sensor failure
– Hardware error
– Converter error
– Leakage pulse error
– Trigger error
0 x 10
bad - sensor failure
– Measured value generation error
– Temperature measurement error
0 x 1f
bad - out of service constant
"Out of Service" mode switched on
0 x 44
uncertain - last unstable value
Failsafe replacement value (Failsafe-Mode = "Last value" and al-
ready valid measured value since switching on)
0 x 48
uncertain substitute set
– Switch on simulation
– Failsafe replacement value (Failsafe-Mode = "Fsafe value")
0 x 4c
uncertain - initial value
Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
0 x 51
uncertain - sensor; conversion
not accurate - low limited
Sensor value < lower limit
0 x 52
uncertain - sensor; conversion
not accurate - high limited
Sensor value > upper limit
0 x 80
good (non-cascade) - OK
OK
0 x 84
good (non-cascade) - active
block alarm
Static revision (FB, TB) changed (10 sec. active, after the parame-
ter of the static category has been written)
0 x 89
good (non-cascade) - active ad-
visory alarm - low limited
Lo-Alarm
0 x 8a
good (non-cascade) - active ad-
visory alarm - high limited
Hi-Alarm
0 x 8d
good (non-cascade) - active crit-
ical alarm - low limited
Lo-Lo-Alarm
0 x 8e
good (non-cascade) - active crit-
ical alarm - high limited
Hi-Hi-Alarm