Dual-Float Discriminating Sensor Alarms
MMM DD, YYYY HH:MM XM
L1 : FUEL ALARM
----SENSOR ALARM----
L 1: ISLAND 1
FUEL ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\28.eps
MMM DD, YYYY HH:MM XM
L1 : HIGH LIQUID ALARM
---- SENSOR ALARM ----
L 1:ISLAND 1
HIGH LIQUID ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\29.eps
14-09-97 19:25:47
L1 : LIQUID ALARM
---- SENSOR ALARM ----
L 1:ISLAND 1
LIQUID ALARM
14-09-97 19:25
consoles\qh\30.eps
MMM DD, YYYY HH:MM XM
L1 : SHORT ALARM
MMM DD, YYYY HH:MM XM
L1 : SENSOR OUT ALARM
---- SENSOR ALARM ----
L 1:ISLAND 1
SENSOR OUT ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\31.eps
CAUSE:
The sensor at the location shown has detected
fuel vapor or liquid.
ACTION:
Silence the alarm by pressing the red ALARM/
TEST key. Investigate the cause of the alarm
and take appropriate action.
CAUSE:
The sensor at the location shown has detected at
least 8 inches of non-hydrocarbon liquid.
ACTION:
Silence the alarm by pressing the red ALARM/
TEST key.
Contact your VR Service Contractor for advice.
CAUSE:
The sensor at the location shown has
detected at least 1 inch of non-hydrocarbon
liquid.
ACTION:
Silence the alarm by pressing the red
ALARM/TEST key. Contact your VR Service
Contractor for advice.
CAUSE:
The sensor at the location shown has been
disconnected or is inoperative.
ACTION:
Silence the alarm by pressing the red
ALARM/TEST key. Contact your VR Service
Contractor for advice.