Page
10
In-Tank Warnings
MMM DD, YYYY HH:MM XM
T1 : HIGH WATER WARNING
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
HIGH WATER WARNING
MMM DD, YYYY HH:MM XM
consoles\qh\US\12.eps
CAUSE:
Water collecting in the tank shown has exceed-
ed the Water Warning level.
ACTION:
Close all pumps attached to this tank. Contact
your VR Service Contractor for advice.
Silence the alarm by pressing the red ALARM/
TEST key.
CAUSE:
Fuel level in the tank shown is below the Deliv-
ery Needed level.
ACTION:
Arrange a delivery.
Silence the alarm by pressing the red Alarm/
Test key.
MMM DD, YYYY HH:MM XM
T1 : INVALID FUEL LEVEL
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
INVALID FUEL LEVEL
MMM DD, YYYY HH:MM XM
consoles\qh\US\13.eps
CAUSE:
Fuel and water level floats on the probe are too
close together due to a lack of fuel in the tank
shown.
ACTION:
Arrange a delivery.
Silence the alarm by pressing the red ALARM/
TEST key.
MMM DD, YYYY HH:MM XM
T1 : DELIVERY NEEDED
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
DELIVERY NEEDED
MMM DD, YYYY HH:MM XM
consoles\qh\US\14.eps
MMM DD, YYYY HH:MM XM
T1 : TANK TEST ACTIVE
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
TANK TEST ACTIVE
MMM DD, YYYY HH:MM XM
consoles\qh\US\15.eps
CAUSE:
If enabled, the system will display this mes-
sage when a requested tank test is in progress.
ACTION:
Do not deliver to or dispense from the tank
being tested.