4.3  INPUT WIRING

CAUTION

: Power input common is NOT isolated from user and input 

commons. In order to preserve the safety of the meter application, the 

power input common must be suitably isolated from hazardous live 

earth referenced voltage; or input common must be at protective earth 

ground potential. If not, hazardous voltage may be present at the signal 

or user inputs and input common terminals. Appropriate considerations must then 

be given to the potential of the user and input commons with respect to earth 

ground; and the common of the plug-in cards with respect to input common.
Before connecting signal wires, the Input Range Jumper should be verified for 

proper position. 

4.4  SETPOINT (OUTPUT) WIRING

COM

N.C.

N.O.

SINGLE SETPOINT RELAY PLUG-IN CARD

Input Signal (self powered)

Series Loop (must use separate supply for sensor power 

and each FLEX MINI)

2 Wire With External Power

2 Wire With RFMPS Power

2 Wire With Separate Sensor And FLEX MINI Power

-

+

COMM

INP+

2 WIRE TRANSMITTER

INP 

+

COMM

EXTERNAL POWER

COMM

+VDC

+

_

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

MLPS1

!

2 WIRE TRANSMITTER

COMM

INP 

+

_

+

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

MLPS1

!

2 WIRE TRANSMITTER

INP 

+

COMM

EXTERNAL POWER

COMM

COMM

+VDC

+VDC

_

+

COMM

INP 

+

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

MLPS1

!

COMM

INP 

+

+VDC

COMM

EXTERNAL POWER

2 WIRE TRANSMITTER

+

_

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

MLPS1

!

COM

N.O.

N.C.

ELECTRICAL CONNECTIONS

DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD

OSNK1

OSNK2

COM

ELECTRICAL CONNECTIONS

Output Common is not isolated from DC Power Common. Load 

must be wired between OSNK terminal and V+ of the load supply.

30 VDC

150 mA

10 VDC

20/50 mA DC

MAX SIGNAL 

INPUT 

JUMPER 

POSITION

COM

OSNK 1(2)

(30 V MAX.)

4.5  SERIAL COMMUNICATION WIRING

N/

C

RS485

2

COMM

A+

B-

N/

C

5

3

4

N/

C

RS232

5

N/

C

TX

N/

C

4 3

COMM

COMM

2

RX

6

1

6

1

4.6  USB PROGRAMMING

USB PROGRAMING PLUG-IN CARD

SERIAL COMMUNICATIONS PLUG-IN CARD

RJ11 CONNECTOR PIN OUTS

20/50 mA DC

JUMPER 

POSITION

20/50 mA DC

JUMPER 

POSITION

20/50 mA DC

JUMPER 

POSITION

20/50 mA DC

JUMPER 

POSITION

Содержание RFMP Series

Страница 1: ...FLEX MINI can be powered from an optional Veeder Root Micro Line Sensor Power Supply MLPS which attaches directly to the back of a FLEX MINI The MLPS is powered from 85 to 250 VAC and provides up to 4...

Страница 2: ...C Green Display 1 2 35 to 75 C 3 35 to 65 C 4 35 to 50 C 5 35 to 35 C Storage Temperature 35 to 85 C Operating and Storage Humidity 0 to 85 max relative humidity non condensing Vibration to IEC 68 2 6...

Страница 3: ...5 SERIAL COMMUNICATIONS CARD Type RS485 multi point balanced interface non isolated Baud Rate 300 to 38 4k Data Format 7 8 bits odd even or no parity Bus Address 0 to 99 max 32 meters per line Transmi...

Страница 4: ...thin an enclosure should be routed as far as possible from contactors control relays transformers and other noisy components 5 In extremely high EMI environments the use of external EMI suppression de...

Страница 5: ...UNREG 400mA 12V DC COMMON M3424B TERMINAL AC INPUT MLPS1 2 WIRE TRANSMITTER COMM INP _ MODEL INPUT POWER OUTPUT POWER 85 250 VAC 50 60Hz 14VA OPERATING TEMP 0 TO 60 C 12VDC UNREG 400mA 12V DC COMMON...

Страница 6: ...the SEL button with Pro NO displayed This will commit any stored parameter changes to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify...

Страница 7: ...Values have to be derived from the actual input signal source or simulator the Apply APLY scaling style must be used KEy APLY 0 000 INP 1 INPUT VALUE FOR SCALING POINT 1 For Key in KEY style enter th...

Страница 8: ...ow FACTORY SERVICE OPERATIONS yES NO YES NO Enables the Maximum Display Capture capability Enables the Minimum Display Capture capability The RFMP uses stored calibration values to provide accurate vo...

Страница 9: ...acklight Unit Only 3 dSP dSP t SEL rSt ZErO UNItS COLOr CodE Display Intensity Level d LEV ScroL Display Scroll Enable PARAMETER MENU The yES selection allows the SEL button to toggle through the enab...

Страница 10: ...ced are affected by the hysteresis When the setpoint is a control output usually balanced hysteresis is used For alarm applications usually unbalanced hysteresis is used For unbalanced hysteresis mode...

Страница 11: ...s Refer to the RFMCOMUSB bulletin for details on the FLEX MINI USB programming and programming requirements PARAMETER MENU button or user input manual reset serial reset command or meter power cycle W...

Страница 12: ...tOF n rSt n rEn n ChC n Standby Operation Stb n Front Panel Reset Enable Front Panel Display Select Enable Display Update Time dSP t SEL rSt 3 dSP Display Intensity Level COLOr Units Indicator Select...

Отзывы: