A-1
Appendix A: Mag-FLEX Safety Information
Equipment Marking
Mag-FLEX probe
1. Manufacturer:
Veeder Root Co., Duncansville, PA – USA
2. Type designation:
Mag-FLEX
3. Certificate number:
TÜV 12 ATEX 105828 – IECEx TUN 12.0027
4. ATEX marking:
II 1 G, II 1/2 G, II 2 G
5. EN/IEC marking:
Ex ia IIB T4 Ga, Ex ia IIB T4 Ga/Gb, Ex ia IIB T4 Gb
6. CE marking:
1180
Intrinsically Safe TLS Tank Gauge System
1. EC-Type Examination Type Certificate: DEMKO 06 ATEX 137480X
2. IECEx Certficate of Conformity:
IECEx ULD 08.0002X
Technical Data
The intrinsically safe input characteristics of the Mag-FLEX probe are listed below. Refer to the site preparation
procedures in this manual for general instructions on safe installation, use and replacement.
The above values are to be used when assembling a system in the field when for calculating its maximum cable run
(field + sensor cable).
When used in potentially explosive atmospheres, the maximum temperatures depending on the temperature
classes and categories can be found in Table A-1.
Parameter
Ui
13 V
Ii
200 mA
Pi
625 mW
Li
410
µH
Ci
20 nF
Table A-1. Temperature Class Ta Tf
Temperature
Class
Ambient Temperature
Range
Medium
Temperature
Category 1 and EPL Ga
(Filling level sensor entirely erected in Zone 0)
T4, T3, T2, T1
-20°C to +60°C
-20°C to +60°C
Category 1/2 and EPL Ga/Gb
(Sensor pipe erected in Zone 0, Sensor head erected in Zone 1)
T4, T3, T2, T1
-40°C to +75°C
-20°C to +60°C
Содержание Mag-FLEX
Страница 1: ...Manual No 577014 038 Revision C Installation Manual EU Version Mag FLEX Probe...