DPLLD Transducer Installation
FE Petro Pumps
18
Figure 14. Location of DPLLD Transducer And Model ‘R’ Precision Check Valve In FE Petro Pump
Figure 15. Identifying A FE Petro ‘R’ Style Precision Check Valve
5. Get a watertight cord grip from the transducer installation kit and coat its 1/2” NPT threaded end with UL-
Classified, nontoxic pipe sealant suitable for the fuel involved. Screw the cord grip into one of the openings in
the weatherproof junction box. Feed the end of the DPLLD transducer cable through the cord grip and then
tighten the nut to ensure a watertight seal. Connect and seal the pressure transducer wires to the wires from
the TLS console as described in ‘Epoxy Sealing DPLLD Transducer Field Wiring Connections’ on page 21.
6. If applicable, open ball valve down line from the pump. Upon start-up of the pump, check for leaks to ensure
that the system is leak free..