Dispenser Pan Sensor Testing

Installing the Dispenser Pan Sensor

16

3.

Install the mounting hardware according to the dispenser pan manufacturer’s 
instructions.

Important 

Mounting hardware should be ordered from the dispenser pan manufacturer. Specify 
that you are installing a Veeder-Root Dispenser Pan Sensor when ordering from the pan 
manufacturer. An optional Veeder-Root Universal Mounting Kit (No. 330020-012) is 
available.

4.

Secure the mounting bracket in the dispenser pan and slide the sensor into position.

5.

Connect the cable from the Dispenser Control Interface to the sensor and secure the 
cable nut.

Important 

For proper sensor operation, sensor connector and cable interface must be dry and free 
from any contaminants.

6.

Tighten the cord grip nut to ensure a watertight seal at the cable entry.

7.

Restore AC power to the junction box.

Dispenser Pan Sensor Testing

After sensor installation, test each dispenser pan sensor with dispenser interface 
installed to be sure it is working properly:

1.

To test the sensor, turn the sensor upside-down. The dispenser should be disabled.

Important 

If the dispenser is not disabled during the test, review the installation instructions in 
“Dispenser Control Interface Installation” on page 5. If
 the sensor does not deactivate 
after you review the installation, contact your Veeder-Root representative or distributor.

2.

To reactivate the dispenser, turn the dispenser power OFF for at least 15 seconds, 
then turn it back ON.

Important 

Final approval of a field installation of this product into an existing dispenser is under 
the authority of the local inspector.

Содержание 847990-001

Страница 1: ...r Pan Sensor with Dispenser Control Interface Non Discriminating Stand Alone Dispenser Pan Sensor With Dispenser Control Interface Part Nos 847990 001 847970 001 Discriminating Stand Alone Dispenser Pan Sensor With Dispenser Control Interface Part Nos 847990 002 847970 002 ...

Страница 2: ...our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313 with the specific part numbers and quantities that were missing or received damaged 2 Fax signed Bill of Lading BOL to Veeder Root Customer Service at 800 234 5350 3 Veeder Root will file the claim with the carrier and replace the damaged missing product at no charge to the customer Cust...

Страница 3: ...gure 4 Typical Installation Wiring Diagram for Dispenser Control Interface to a Dresser Wayne Dispenser 120 VAC 8 Figure 5 Typical Installation Wiring Diagram for Dispenser Control Interface to a Gilbarco Dispenser 120 VAC Models 9 Figure 6 Typical Installation Wiring Diagram for Dispenser Control Interface to a Tokheim Basic TCS Model 614 628 Dispenser 10 Figure 7 Typical Installation Wiring Diag...

Страница 4: ...Control Interface Part No 847970 001 Float Switch Type Veeder Root Discriminating Stand Alone Dispenser Pan Sensor with Dispenser Control Interface Part No 847970 002 Differentiating Type The above parts are designed and manufactured by Veeder Root This manual assumes all preliminary site preparation is completed and that field wiring to the dispenser junction box is in place Safety Symbols The fo...

Страница 5: ...njury Careless or improper handling of materials can result in bodily injury Gloves Wear gloves to protect hands from irritation or injury OFF WARNING This product is to be installed in systems operating near locations where highly combustible fuels or vapors may be present Fire or explosion resulting in serious injury or death could result if the equipment is improperly installed or modified Seri...

Страница 6: ...er Root Non Discriminating Stand Alone Dispenser Pan Sensor with Dispenser Control Interface Part No 847970 001 Float Switch Type Veeder Root Discriminating Stand Alone Dispenser Pan Sensor with Dispenser Control Interface Part No 847970 002 Differentiating Type For both 1 Wiring Kit Part No 330020 024 Installation Instructions Important Mounting brackets are required and must be ordered separatel...

Страница 7: ...g to open the junction box and wire the dispenser control interface to the dispenser The following applies to both installing and wiring the Dispenser Control Interface Important 2 The junction box must have sufficient volume to accommodate the extra wiring to be installed and must comply with the National Electric Code Article 370 16 The required volume for any dispenser can be calculated using t...

Страница 8: ...A conductor passing through the box and each conductor terminating in the box is counted as one conductor No unplugged openings are permitted WARNING Before installing this device turn OFF power to the system Electrical shock resulting in serious injury or death may result if power is on during installation and the device is improperly installed High voltages are present in the dispenser junction ...

Страница 9: ...cal Dispenser Control Interface Installation 5 For Discriminating Dispenser Pan Sensor with Dispenser Control Interface Part Nos 847990 002 and 847970 002 attach the CAUTION Tag to the dispenser pan in a visible area 6 Any additional parts required to allow the interface to clear the parts adjacent to the junction box conduit opening must be provided by the installer At least 5 full threads must b...

Страница 10: ...Interface See Figure 3 on page 8 Dispenser Control Interface Wiring 1 Wire Dispenser Control Interface to dispenser according to the appropriate Dis penser Control Interface wiring diagram Figure 3 on page 8 Figure 4 on page 8 Figure 5 on page 9 Figure 6 on page 10 Figure 7 on page 11 Figure 8 on page 12 or Figure 9 on page 13 WARNING To maintain intrinsic safety route cable in accordance with Art...

Страница 11: ...gure 3 Typical Dispenser Control Interface Wiring Diagram Figure 4 Typical Installation Wiring Diagram for Dispenser Control Interface to a Dresser Wayne Dispenser 120 VAC 845 3 DISPENSER DISPENSER POWER NEUTRAL 120 VAC COMBINED MAXIMUM 120V 8A RESISTIVE 1A PILOT DUTY RELAY CONTACT RATING RED PAN SENSOR DISPENSER CONTROL INTERFACE WHT BLK RED INPUT 120VAC 4 5 VA 50 60 Hz NEUTRAL COMBINED MAXIMUM 1...

Страница 12: ...g 9 Figure 5 Typical Installation Wiring Diagram for Dispenser Control Interface to a Gilbarco Dispenser 120 VAC Models COMBINED MAXIMUM 120V 8A RESISTIVE 1A PILOT DUTY RELAY CONTACT RATING PAN SENSOR DISPENSER CONTROL INTERFACE INPUT 120VAC 4 5 VA 50 60 Hz NEUTRAL 845 5 ...

Страница 13: ...cal Installation Wiring Diagram for Dispenser Control Interface to a Tokheim Basic TCS Model 614 628 Dispenser COMBINED MAXIMUM 120V 8A RESISTIVE 1A PILOT DUTY RELAY CONTACT RATING PAN SENSOR DISPENSER CONTROL INTERFACE INPUT 120VAC 4 5VA 50 60 Hz NEUTRAL 845 6 WHT BLK SYSTEM EARTH GROUND ...

Страница 14: ...11 Figure 7 Typical Installation Wiring Diagram for Dispenser Control Interface to a Tokheim 262 Series Dispenser 845 7 COMBINED MAXIMUM 120V 8A RESISTIVE 1A PILOT DUTY RELAY CONTACT RATING PAN SENSOR DISPENSER CONTROL INTERFACE INPUT 120VAC 4 5 VA 50 60 Hz NEUTRAL WHT BLK ...

Страница 15: ... Typical Installation Wiring Diagram for Dispenser Control Interface to a Tokheim 262A Series Dispenser 845 8 COMBINED MAXIMUM 120V 8A RESISTIVE 1A PILOT DUTY RELAY CONTACT RATING PAN SENSOR DISPENSER CONTROL INTERFACE INPUT 120VAC 4 5 VA 50 60 Hz NEUTRAL BLK WHT SYSTEM EARTH GROUND ...

Страница 16: ...Typical Installation Wiring Diagram for Dispenser Control Interface to a Tokheim Premier Series Dispenser 845 9 COMBINED MAXIMUM 120V 8A RESISTIVE 1A PILOT DUTY RELAY CONTACT RATING PAN SENSOR DISPENSER CONTROL INTERFACE INPUT 120VAC 4 5 VA 50 60 Hz NEUTRAL WHT BLK SYSTEM EARTH GROUND ...

Страница 17: ...ese guidelines to help insure proper operation of the sensor The sensor should rest in the cup or lowest point of the dispenser pan The sensor should be mounted in a true vertical position where it can be pulled straight out for future service or replacement If installing the sensor into a backfilled pan it is recommended that a screen tube be used for ease of removal and reinstallation Refer to F...

Страница 18: ...e sensor straight up out of the pan 3 Be mounted in a true vertical position Dispenser pan sensor sensors dpsnsts2 eps U channel Screen shown for backfilled applications sensors dpsndss2 eps Brackets clamp etc from Universal sensor mounting kit Dispenser pan sensor should 1 Rest in the cup or the lowest point of the dispenser containment sump 2 Be positioned so as to be removable when pulling the ...

Страница 19: ...d free from any contaminants 6 Tighten the cord grip nut to ensure a watertight seal at the cable entry 7 Restore AC power to the junction box Dispenser Pan Sensor Testing After sensor installation test each dispenser pan sensor with dispenser interface installed to be sure it is working properly 1 To test the sensor turn the sensor upside down The dispenser should be disabled Important If the dis...

Страница 20: ...For technical support sales or other assistance please visit www veeder com ...

Отзывы: