1
Introduction
Before You Begin
1-4
Before You Begin
Prior to backfilling the tank top (i.e. covering the lines, UDC, etc.) the contractor is strongly advised to test all of
the secondary containments for leaks, and to monitor the vacuum during the backfill process. Any leakage
detected must be repaired to prevent future vacuum system alarms.
Do not exceed equipment manufacturer’s recommended vacuum levels
!
While it is common practice to use an independent vacuum source to provide the initial vac-
uum, you must ensure that pump lubricating oil and any other foreign substance is not intro-
duced into the SCVS system. Failure to do so may damage the SCVS system and will void
warranty.
WARNING
This product is to be installed in systems operating near locations where
highly combustible fuels or vapors may be present.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT,
RESULTING IN SERIOUS INJURY OR DEATH.
1. Read and follow all instructions in this manual, including all safety warnings to
protect yourself and others from serious injury, explosion, or electrical shock.
2. Comply with all applicable codes including: the National Electrical Code;
federal, state, and local codes; and other applicable safety codes.
3. To protect yourself and others from being struck by vehicles, block off your
work area during installation or service.
4. Turn off, tag, and lockout power to the STP before connecting or servicing
wiring to the STP.
5. Do not alter or modify any component or substitute components in this kit.
6. Substitution of components may impair intrinsic safety.
7. Field wiring to the Sensor must not share a conduit with any non-intrinsically
safe device’s wiring.
8. Before installing or taking the unit into a hazardous area, earth the unit in a
safe area to remove any static charge. Then immediately transport the unit to
the installation site. Do not rub or clean the unit prior to installation. Cleaning
is not required under normal service conditions. Do not rub or clean the unit
after installation. If the unit is not fixed to a known earth point when installed,
ensure that a separate earth connection is made to prevent the potential of a
static discharge. When fitting or removing the unit, use of anti-static footwear
or clothing is required.
9. Materials used in the construction of this device do not contain, by mass, more
than 10% in total of aluminum, magnesium, zirconium and titanium or 7.5% in
total of magnesium, titanium and zirconium.
OFF
CAUTION
NOTICE