TLC3-FCR-M Engineering Manual

 

 

Doc: 70-00-0181, V3.0 Date: 20120424 

© Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

Display and Operation 

 

Operation mode 

 

Comfort (occupied) 

All control functions operating per set points. 

 

Economy (unoccupied): 

Set points shifted according to 

Parameters FC04.

 

Economy mode and setpoint shift may be disabled with UP06 

OFF 

Energy Hold Off 

Outputs are off, inputs monitored for alarm condition 

 

Heating 

Output activates if temperature lower than setpoint 

 

Cooling 

Output activates if temperature higher than setpoint 

 

Fan 

Fan is running, the vertical bars show active speed 1-3 

 

Manual mode 

Manual override of fan speed, fan only mode or override of time schedule active.  

 

Schedule 

Deluxe only: Time schedule is active 

Power Failure 

All the parameters and set points are memorized and do not need to be reentered. Depending on 

UP05

 the unit will 

remain switched off, switch on automatically or return to the operation mode it was in before the power failure. 

Deluxe version only

: Timer operation and daytime setting will be retained for 24h. The controller has to be connected 

to a power supply for at least 10 hours for the backup function to operate accordingly.  

Frost Protection 

The controller will enter frost protection mode if the room temperature drops below 5°C (41°F). All heating outputs will 

be fully opened. Frost protection mode will be left once the temperature reaches 10°C  (50°F). Frost protection display 

will remain until a button is pressed. Frost protection can be enabled/disabled using user parameter UP-09 

Error messages 

Following error condition may be shown: 

Err1:

 

The connection to the temperature sensor may be interrupted or the temperature sensor is damaged.  

The output is switched off. Verify parameter settings and wiring.  

FP:

 

Steady: Frost protection is active.  

Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key. 

 

 

 

Left (POWER):  

Press < 2 sec.: Toggle Economy - 
Comfort mode or switch from OFF 
to ON 

Press > 2 sec.: Turn unit OFF. Text 
OFF displayed with current time 
(deluxe) temperature (standard) 

(Parameter setting: Return to 
previous level. ESC) 

 

Up :  

Increase setpoint  

(Parameter setting: 
scroll menu options 
and parameters) 

 

Down:  

Decrease setpoint  

(Parameter setting: scroll menu 
options and parameters) 

 

Mode 

Display of operation 

mode 

 

 

Large Digits 

Display of input or parameter value. 

Indicators 

1 Remote 

temperature sensor 

Vertical Bar 

(fan speeds 1-3 or proportional 
output in 10% steps) 

Small Digits 

Display of setpoint, clock or 
parameter number. 

 

Right (OPTION)  

Press < 2 sec.: Select fan speed: 
Low, medium, high or auto 

Press > 2 sec.: Manual H/C change 

(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 

 

Содержание TLC3-FCR-M2-24

Страница 1: ...l controller with one control loop The TLC3 FCR M2 is designed for 2 pipe modulating fan coil systems and features 1 NTC temperature sensor input one external passive input for temperature or open con...

Страница 2: ...Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive L...

Страница 3: ...lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance c...

Страница 4: ...t protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection displ...

Страница 5: ...d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One ba...

Страница 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Страница 7: ...t points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time pr...

Страница 8: ...witched on ON OFF OFF FC 09 Switching delay min running time of fan speed Prevents the fan from switching in too short intervals 0 255 s 10s FC 10 Switching delay min stopping time of fan speed Preven...

Страница 9: ...tion detectors for offices FC19 3 Switching Energy Hold OFF and Comfort modes Opening the input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the ter...

Страница 10: ...TLC3 FCR M Engineering Manual Doc 70 00 0181 V3 0 Date 20120424 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Отзывы: