TLC3-FCR-M Engineering Manual

 

 

Doc: 70-00-0181, V3.0 Date: 20120424 

© Vector Controls GmbH, Switzerland 

Page 5 

Subject to alteration 

Manual heat – cool change 

To manually change heating or cooling mode press the OPTION key for more than 2 seconds. Access to manual heat – 

cool change may be disabled by parameters. 

For standard models: Press OPTION > 2 sec. SEL and H-C is displayed.  
For deluxe models: Press OPTION > 2 sec. SEL and current time is displayed.  
 

Press UP key twice. SEL and H-C is displayed. 

Press OPTION again to toggle Heating, Cooling and Fan only modes.  

SEL 
  H-C 

 

 

 

Clock operation  

The deluxe model contains a quartz clock with battery back-up. Up to 4 time schedules with each 4 mode changes 

based on time and day of the week may be programmed. A blinking clock indicates that the time has not been set or if 

the unit was without power for longer than 48 hours. The time needs to be set to allow time schedules to operate. 

 

Clock setup 

Press OPTION > 2 sec. SEL and current time displayed 
Press OPTION < 2 sec. to change time, 

Minutes blink: UP/DOWN to changes, OPTION to save,  
Hours blink: UP/DOWN to changes, OPTION to save,  

Press OPTION to save time, 

DAY1 blinks: UP/DOWN to change, OPTION to save 

SEL 
  00:00  
  DAY1 (Mon) 

 

Creating time schedules  

Step 1: Selection and enabling of time schedules 

Press OPTION > 2 sec. SEL and current time displayed 
Press UP:  

SEL and PRO displayed, clock symbol blinks 

Press OPTION:  

PRO1 shows with 1 blinking. UP/DOWN select time schedule group 

Press OPTION 

OFF/ ON blinks, UP/DOWN to change, OPTION to save  

SEL 
  PRO 

  

 

Pro1-Pro4 
  OFF/ON 

   

Step 2: Select weekdays 

This time schedule will be active during the selected weekdays  
Press UP/DOWN to step through available options:  

d1-7, d1-6, d1-5, d6-7, day1, day2, day3, day4, day5, day6, day7 
Day 1 stands for Monday, day 2 for Tuesday and so forth 

Press OPTION to save day selection 

   

Pro1 
  d1-7

 

 

Step 3: Selected action of first switching event  

One bar on the right side indicates the first switching event 
Press UP/DOWN to select action for first switching event: 

No =   switching event not active 
OFF =   switches unit off, Reset (UP17) active if switched to ON manually.  
Eco =   sets operation mode to On and Economy (Not occupied),  
  

reset (UP17) active if set to comfort manually 

On =   sets operation mode to On and Comfort (Occupied) 
Uni =   University mode, Reset (UP17) not active if manually activated 

Press OPTION to select switching time of first event 

  

Pr01 

    no 

 
 

 Step 4: Selected time of first switching event  

Press UP/DOWN to select switching time: 

Select switching time 00:00 to 23:45 in 15-minute steps  

Press OPTION to complete and select action of second switching event 

  

Pr01 

   08:00

 

Step 5: Select actions and time of switching event 2 - 4  

Repeat Step 3 and Step 4 for the remaining switching events.  

If a switching event is not needed, set it to “no” 
The bars on the right side indicate number of switching event 

After completing the 4

th

 switching event, the process returns to the selection of the time schedule on step 1.  

  

Pr01 

   08:00

 

 

 

UNI: University mode: This switching mode is used for rooms such as lecture rooms and auditoriums that might 

be occupied during a certain time. During this time the reset is not active. The unit will not start itself when UNI 

mode is active. It still needs to be manually activated. This is to avoid unnecessary heating or cooling of such 

rooms while they are not occupied.  

 

A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined. 

See chapter operation, advanced settings for instructions on how to set the time. 

 

Access to time schedules may be disabled with UP-04 

Содержание TLC3-FCR-M2-24

Страница 1: ...l controller with one control loop The TLC3 FCR M2 is designed for 2 pipe modulating fan coil systems and features 1 NTC temperature sensor input one external passive input for temperature or open con...

Страница 2: ...Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive L...

Страница 3: ...lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance c...

Страница 4: ...t protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection displ...

Страница 5: ...d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One ba...

Страница 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Страница 7: ...t points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time pr...

Страница 8: ...witched on ON OFF OFF FC 09 Switching delay min running time of fan speed Prevents the fan from switching in too short intervals 0 255 s 10s FC 10 Switching delay min stopping time of fan speed Preven...

Страница 9: ...tion detectors for offices FC19 3 Switching Energy Hold OFF and Comfort modes Opening the input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the ter...

Страница 10: ...TLC3 FCR M Engineering Manual Doc 70 00 0181 V3 0 Date 20120424 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...