Fan Coil Controller TLC3-FCR-M-U-24 

 

 

Fan Coil Controller TLC3-FCR-M-U-24 

 

 

Fan Coil Controller TLC3-FCR-M-U-24 

 

Doc: 70-00-0271-50, V3.0, 20130104 

© Vector Controls GmbH, Switzerland 

Subject to alteration 

TLC3-FCR-M-U-24, Programmable PI Fan Coil Controller 

Features 

 

Proven PI controls algorithm reduces room temperature fluctuations and energy consumption 

 

Low power energy consumption: < 1W per unit 

 

Relays switching for outputs each up to 300W 

 

Temperature control for 2 or 4-pipe fan coil systems.  

 

Automatic fan control for three stage fans.  

 

Cost saving option with Economy functionality and set point limitations 

 

Control for modulating heating, cooling and fan only operation modes 

Deluxe Version: 

 

Clock and time schedule functions with power failure clock protection 

 

Blue backlight for LCD 

 

Infrared remote controller option:  
With special features for Boost and delayed switching on or off 

Ordering 

Item Name 

Item code 

Variant 

Power 

Features 

TLC3-FCR-M2-U-24 

40-10 0141 

Standard 

24VAC/DC 

Fan coil controller with:  
1 TI int, 1 external input 
3 DO (Relay) Fan control 
1 AO (0-10VDC) PI valve control 

TLC3-FCR-M2-U-120 

40-10 0151 

120VAC 

TLC3-FCR-M2-U-230 

40-10 0102 

230VAC 

TLC3-FCR-M2-U-D-24 

40-10 0146 

Deluxe 

24VAC/DC 

TLC3-FCR-M2-U-D-120 

40-10 0156 

120VAC 

TLC3-FCR-M2-U-D-230 

40-10 0103 

230VAC 

TLC3-FCR-M4-U-24 

40-10 0142 

Standard 

24VAC/DC 

1 TI int 
3 DO (Relay) Fan control 
2 AO (0-10VDC) PI valve control 

TLC3-FCR-M4-U-120 

40-10 0152 

120VAC 

TLC3-FCR-M4-U-230 

40-10 0106 

230VAC 

TLC3-FCR-M4-U-D-24 

40-10 0147 

Deluxe 

24VAC/DC 

TLC3-FCR-M4-U-D-120 

40-10 0157 

120VAC 

TLC3-FCR-M4-U-D-230 

40-10 0107 

230VAC 

-W01 

-1 

Cooling only 

 

Add to name or code for special 
settings 

Selection of fans 

Do not directly connect devices that exceed 2A. Observe startup current on inductive loads! Do not connect 
more than one fan coil unit to one controller. 

Modulating Actuators:  

Choose actuators with an input signal type of 0-10V DC or 2-10V DC. Observe maximal signal current of 
1mA! 

Mounting location 

  Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of 

average temperature. 

  Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

  Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

  Location of mounting is less critical if external temperature sensors are used. 

Installation 

1. 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2. 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding 
screw is facing to the ground. Make sure the mounting screw heads do not stand out more than 5 
mm (0.2”) off the surface of the mounting plate.  

3. 

Slide the two latches located on the top of the front part into the hooks at the upper side of the 
mounting plate.  

4. 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue 
pressing in a gentle way until the front part is fully connected. While inserting the connectors, a 
slight resistance can be felt. This is normal. Do not use excessive force!  

5. 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the 
front part to the mounting plate. This screw is located on the front lower side of the unit. There is no 
need to tighten the screw too much. 

Power Failure 

Upon power-interruption, all parameters and setpoints are memorized in non-volatile memory and therefore 
do not have to be re-entered again. 

Error messages 

Err1:

 

Error temperature sensor. The internal temperature sensor may be damaged or not present.  

FP:

 

Steady: Frost protection is active.  
Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key. 

 

Display and Operation 

 

Technical Specification 

Power Supply 

Operating Voltage 
Transformer 

24 VAC ±10%, 50/60 Hz, 24VDC ±10% 
SELV to HD 384, Class II, 48VA max 

 

Power Consumption 

Max 1W, 1.5VA 

 

Electrical Connection 

Terminal Connectors 

 

Deluxe type only: Power backup for real time clock 

Min 48h if charged for 24h 

Signal Inputs 

Temperature Inputs 

Range 
Accuracy 

RT Int., Ext. (Sxx-Tn10 sensor) 
0…50 °C (32…122 °F) 
0.5°C (1°F) 

Signal Outputs 

Digital Switching Outputs 

Switching Type 
Switching power 

DO1 to DO3 
Relays 
2A max. each output 

 

Analog Outputs 

Output Signal 
Minimum impedance / maximum load 

AO1, For TLC3-FCR-M4 AO2  
DC 0...10 V 
10kOhm, 1mA.  

 

Operation 

Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0°C …50°C (32°F…122°F) 
<95% R.H. non-condensing 

Environment 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25°C…70°C (-13°F…158°F) 
<95% R.H. non-condensing 
class 2M2 

 

 

conformity 
EMC Directive 
Low Voltage Directive 

2004/108/EC 
2006/95/EC 

Standards 

Product standards 
Automatic electrical controls for household and similar use 
Special requirement on temperature dependent controls 

 
EN 60 730 –1 
EN 60 730 – 2 - 9 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60 730-1 
Immunity: EN 60 730-1 

 

Degree of Protection 

IP30 to EN 60 529 

 

Pollution Class 

II (EN 60 730-1) 

 

Safety Class:  

 

III (IEC 60 536)  

 

Overvoltage Category:  

I (EN 60 730-1) 

 

RoHS  

Compliant 

General 

Dimensions (H x W x D)  Front part:  

Power case: 

16 x 73 x 113mm (0,7 x 2.9 x 4.5 in.)  
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) 

 

Material:  

Cover, back part 
Mounting Plate 

ABS plastic (UL94 class V-0) 
Galvanized Steel 

 

Weight (including package) 

Standard:  

270g (9.5oz) 

Deluxe (-D):  

275g (9.7oz) 

Wiring Diagram 

 

Description:  

Power supply:  

0V Neutral 

Power supply:  

24V AC/DC 

Y1 

Binary output:  

Fan speed low 

Y2 

Binary output:  

Fan speed medium 

Y3 

Binary output:  

Fan speed high 

 
TLC3-FCR-M2-U: 

 

Signal common:  

Common 0 potential for inputs and analog outputs. 

X1

 

External input: 

NTC 10kΩ @ 25°C (77°F) or open contact to SGND 

U1

 

Analog output:  

0…10 V DC 

 
TLC3-FCR-M4-U: 

Signal common:  

Common 0 potential for inputs and analog outputs. 

U2

 

Analog cooling output:  

0…10 V DC

  

U1

 

Analog heating output:  

0…10 V DC 

Dimensions 

 

32 (1.3) 

16 (0.7) 

11

3 (4.

5)

 

73 (2.9) 

Space required in flush mounting box: (H x W x D) 60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) 
Distance for mounting screws: Horizontal and vertical: 45 to 63mm (1.8 to 2.5 in.) 

X

T INT 

0V 

24V AC/DC 

 


TLC3-FCR-M2-U-24 

X1 

X

T EXT

  

IN 

 

U1 

AO1 

 

Y1 

Fan 

Low 

Y2 

Fan 

Med 

Y3 

Fan 

High 

SGND 

 

X

T INT 

0V 

24V AC/DC 

 


TLC3-FCR-M4-U-24 

U1 

AO1 

Heat 

 

Y1 

Fan 

Low 

Y2 

Fan 

Med 

Y3 

Fan 

High 

SGND 

U2 

AO2 
Cool 

 

Left (POWER): 

Press < 2 sec.: Toggle 

Economy - Comfort mode or switch from 
OFF to ON 
Press > 2 sec.: Turn unit OFF. Text OFF 
displayed with current time (deluxe) 
temperature (standard) 
(Parameter setting: Return to previous 
level. ESC) 
 

Up : 

Increase setpoint  

(Parameter setting: scroll 
menu options and 
parameters) 
 

Down: 

Decrease setpoint 

(Parameter setting: scroll menu 
options and parameters) 
 

Mode 

Display of operation mode 

 
 

Large Digits: 

Display of input 

or parameter value. 

Indicators 

1 Remote temperature 

sensor 

Vertical Bar: 

Fan speed or 

proportional output 

Small Digits: 

Display of 

setpoint, clock or parameter 
number. 
 

Right (OPTION)  

Press < 2 sec.: Select fan speed: 
Low, medium, high or auto 
Press > 2 sec.: Manual H/C change 
(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 
 