Display and Operation 

The operation terminal uses an LCD display and four operation buttons.  

                                                          

                                                         Legend: 

 

1.

 

4-digit display of current value, 
Minimum, Maximum or control 
parameter 

2.

 

Unit of displayed value, °C, °F, % or 
none 

3.

 

Graphical display of output or input 
signal with a resolution of 10% 

4.

 

4-digit display of current value or 
control parameter 

5.

 

Left bar = display of minimum value 
Right bar = display of maximum value 

6.

 

Buttons for operating the controller: 
LEFT key:   

Operation mode (On, Off) Not used 

UP key:    

Display Maximum values, pressing for more than 2 seconds resets Maximum value 

DOWN key: 

Display Minimum values, pressing for more than 2 seconds resets Minimum value 

RIGHT key: 

Select transmitter, For transmitters with more than one input.  

Operation of the Terminal Unit 

Idle display 

Single input transmitters: The current, minimum or maximum value is shown in the large digits. The small digits indicate 

the active input. (IN 1). The vertical bar on the right side indicates the actual output voltage or current in 10% steps.  
Combination transmitters: The idle display mode is active if no key has been pressed during the previous 30 seconds.  The 

current temperature (IN 1) is displayed in the large digits and the humidity or pressure (IN 2) is displayed in the small 

digits. Pressing the RIGHT key will step through available sensor inputs. Indicating the current, minimum or maximum 

value in the large digits and indication of input number in the small digits and the output signal in the vertical bar.  

Indication and reset of minimum and maximum values 

Activate the desired transmitter for dual transmitter by pressing the RIGHT key. Press UP to display Maximum values, 

press DOWN key to display minimum values.  
Resetting minimum or maximum values: Pressing either UP or DOWN keys for longer than 3 seconds while the minimum 

or maximum values are displayed.   

Error messages 

The OPC-S may display the following error condition:  

Err1:

  Communication time out between terminal unit and transmitter. Terminal unit will reset after 10 

seconds.   

Err2:

  Temperature sensor faulty. The connection to the temperature sensor may be interrupted or the 

temperature sensor is damaged. As a consequence the output of this transmitter are switched off. 

 