Input configuration 

Parameter  Description 

Range 

Default 

IP 00 

Not used 

IP 01 

CI1: Samples taken for averaging control signal 

1)

 

1…255

 

10 

IP 02 

CI1: Calibration 

-

10…10%

 

IP 03 

CI1: Minimum CO2 range ppm 

(CO2 level when output is at its minimum) 

0…50

00 ppm 

0 ppm 

IP 04 

CI1: Maximum CO2 range ppm 

(CO2 level when output is at its maximum) 

0…

5000 ppm 

2000 ppm 

IP 05 

CI1: Enable ABC automatic CO2 background calibration 

ON, OFF 

ON 

IP 06 

CI1: Calibrate CO2 sensor 

Note: For normal operation, calibration is not required. Only experts 

should calibrate the sensor.  

0 = No calibration (default) 
1 = Calibrate to gas (0 ppm) 

2 = Calibrate to fresh air (400 ppm) 

4 = Calibration error (status) 

0

1)

 Sample interval: 1 sec. 

Output configuration 

Parameter  Description 

Range 

Default 

OP 00 

AO1 (CO2): Configuration of output signal: 

0 = CO2 value 

1 = Recorded minimum CO2 value 

2 = Recorded maximum CO2 value 

0

OP 01 

AO1 (CO2): Minimum limitation of CO2 output signal 

2) 3)

 

0

…100

 % 

0 % 

OP 02 

AO1 (CO2): Maximum limitation of CO2 output signal 

2) 3)

 

0…

100 % 

100 % 

2)

 The Output signal will be scaled according to selected input range, selected limitation of output signal and the output 

signal range selected by the jumper. 

3)

 If the default values are changed, the position of JP2 has no influence and the output signal range defined with the 

parameters applies. 

IP 

=  Input Parameter 

OP  =  Output Parameter 
CI 

=  CO2 Input 

AO  =  Analog Output 

 

Examples of CO2 output signal on AO1: 

Output signal type = Voltage (JP1 jumper setting) 

Output signal range = 0…10 VDC (JP

4 jumper setting) 

 

Default setting 

Custom setting 

IP 03 = 0 ppm, IP 04 = 2000 ppm (range) 

IP 03 = 0 ppm, IP 04 = 2000 ppm (range) 

OP 00 = 0 (CO2 value) 

OP 01 = 0 % (limitation) 

OP 02 = 100 % (limitation) 

OP 00 = 0 (CO2 value) 

OP 01 = 20 % (limitation) 

OP 02 = 80 % (limitation) 

 

100%

10 V

0%

0 V

0

2000

ppm

Output

0

2000

ppm

Output

20%

2 V

80%

8 V

 

 

 

 

Содержание SDC-C1

Страница 1: ...er to reach the given accuracy it is required that the sensor is for at least 3 weeks in operation NOTE The ABC calibration works only in those applications where the CO2 concentration sinks regularly...

Страница 2: ...tputs Analog outputs Output signal Resolution Maximum load 0 10 VDC 0 20 mA or 2 10 VDC 4 20 mA 10 bit 9 7 mV 0 019 5 mA Voltage signal 1k current signal 250 Environment Operation Climatic conditions...

Страница 3: ...ion on page 5 Mounting instruction See SDC C1 installation sheet no 70 000573 www vectorcontrols com Dimension mm inch 2 10V 4 20mA 0 10V 0 20mA Range STATUS LED OPA S VDC mA AO1 JP4 JP1 OPC S Sensor...

Страница 4: ...the UP key for at least 5 seconds and wait until the value changes Use of OPC S 1 Press the UP key to see the maximum values or the DOWN key to see the minimum values 2 To reset the minimum value pre...

Страница 5: ...he UP and DOWN keys to set the password 0009 and confirm with the RIGHT key 5 Select IP SEL Input Parameter or OP SEL Output Parameter with UP and DOWN and confirm with the RIGHT key The first paramet...

Страница 6: ...ameter Description Range Default OP 00 AO1 CO2 Configuration of output signal 0 CO2 value 1 Recorded minimum CO2 value 2 Recorded maximum CO2 value 0 2 0 OP 01 AO1 CO2 Minimum limitation of CO2 output...

Страница 7: ...r level of CO2 could prevent a stable signal Observe the CO2 value on the OPA S 2 Once the CO2 value has stabilized login with the OPA S and set IP 06 2 then exit configuration mode The air quality le...

Страница 8: ...20405 Vector Controls GmbH Switzerland Page 8 8 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzer...

Отзывы: