background image

 

SDC-C1 

D

UCT 

CO2

 

T

RANSMITTER

 

 

Doc: 70-00-0399A, V2.9, 20220405  

© Vector Controls GmbH, Switzerland  

Page 2-8 

Subject to change without notice  

www.vectorcontrols.com 

Technical Specifications 

 

Power supply 

Operating voltage 

24 VAC 50/60 Hz ± 10%, 24 VDC ± 10% 

Power consumption 

Max. 2 VA 

Safety extra-low voltage (SELV) 

HD 384, class II 

Connection 

Terminal connectors 

For wire 0.34…2.5 mm

2

 

(AWG 24…12)

 

CO2 measurement 

Sensing method  

Non-dispersive infrared (NDIR) waveguide technology 

with ABC automatic background calibration algorithm 

 

Sampling method 

Diffusion 

 

Response time (90%) 

2 Minutes 

 

Measurement range 

0 - 5000 ppm 

vol.

 

 

Repeatability 

± 20 ppm ± 1 % of measured value 

 

Accuracy 

± 40 ppm ± 3 % of measured value 

 

Pressure dependence 

+ 1.6 % reading per kPa deviation from normal 

pressure, 100 kPa 

Signal outputs 

Analog outputs 

Output signal 

Resolution 

Maximum load 

 

0

10 VDC, 

0…20

 mA 

or 2…10 V

DC

, 4…20 mA

 

10 bit, 9.7 mV, 0.019.5 mA 

Voltage s

ignal: ≥1kΩ, 

current s

ignal: ≤

2

50Ω

 

Environment 

Operation 

Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 

class 3 K5 

0…

50 

°C (32…1

22 °F) 

<85% RH non-condensing 

 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3 K3 and class 1 K3 

-3

0…70

 °C (-22

…158

 °F) 

<95% RH non-condensing 

class 2M2 

Standards 

Degree of protection 

IP30 to EN 60 529 

Safety class 

III (IEC 60536) 

Housing materials 

Cover, back part 

PC+ABS (UL94 class V-0) 

General 

Dimensions (H x W x D) 

Transmitter case 
Probe 

 
68 x 91 x 47 mm (2.7 x 3.7 x 1.9 in) 
Ø 14 x 160 mm, (Ø 0.55 x 6.2 in) 

 

Weight (including package) 

290 g (10.2 oz.) 

 

Product testing and certification 

 

Declaration of 

Conformity 

Information on the conformity of our products can be found on our website 

www.vectorcontrols.com

 on the corresponding product page under "Downloads". 

 

 

 

Содержание SDC-C1

Страница 1: ...er to reach the given accuracy it is required that the sensor is for at least 3 weeks in operation NOTE The ABC calibration works only in those applications where the CO2 concentration sinks regularly...

Страница 2: ...tputs Analog outputs Output signal Resolution Maximum load 0 10 VDC 0 20 mA or 2 10 VDC 4 20 mA 10 bit 9 7 mV 0 019 5 mA Voltage signal 1k current signal 250 Environment Operation Climatic conditions...

Страница 3: ...ion on page 5 Mounting instruction See SDC C1 installation sheet no 70 000573 www vectorcontrols com Dimension mm inch 2 10V 4 20mA 0 10V 0 20mA Range STATUS LED OPA S VDC mA AO1 JP4 JP1 OPC S Sensor...

Страница 4: ...the UP key for at least 5 seconds and wait until the value changes Use of OPC S 1 Press the UP key to see the maximum values or the DOWN key to see the minimum values 2 To reset the minimum value pre...

Страница 5: ...he UP and DOWN keys to set the password 0009 and confirm with the RIGHT key 5 Select IP SEL Input Parameter or OP SEL Output Parameter with UP and DOWN and confirm with the RIGHT key The first paramet...

Страница 6: ...ameter Description Range Default OP 00 AO1 CO2 Configuration of output signal 0 CO2 value 1 Recorded minimum CO2 value 2 Recorded maximum CO2 value 0 2 0 OP 01 AO1 CO2 Minimum limitation of CO2 output...

Страница 7: ...r level of CO2 could prevent a stable signal Observe the CO2 value on the OPA S 2 Once the CO2 value has stabilized login with the OPA S and set IP 06 2 then exit configuration mode The air quality le...

Страница 8: ...20405 Vector Controls GmbH Switzerland Page 8 8 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzer...

Отзывы: