Display & Operation 

ON/OFF operation 

The device is activated by pressing the ON/OFF button. 

Depending on the position of JP1, the minimum air volume 

remains active even during OFF mode. In OFF mode, the 

operating mode symbol lights up with reduced intensity 

Manual operation 

The following operation modes will be activated through 

repeated pressing of the Level button:  
Level 0 = Minimum air volume 

Level 1 

Level 2 

Level 3 = Maximum air volume 

Auto operation 
 

The operating modes are activated after 2 seconds. This 

prevents unnecessary switching when setting the device. 

The Level-indication and buttons light up in green or blue 

depending on the type of device.  

The device is equipped with proximity detection. When approaching a distance of approx. 10 cm, the luminosity of the 

LED increases. After 30 seconds without interaction, the LEDs dim down again and thus save energy. 

AUTO operation 

The automatic operation of the device is enabled once a sensor signal is detected at the input. During AUTO operation the 

levels are switched by a control signal. The switching levels are defined under IP04 

 IP06.  

The hysteresis defined with IP07 prevents rapid switching of levels in auto mode.  
Function: A level activates once the input signal exceeds the activation limit (IP04-IP06). It deactivates once the input 

signal drops below the activation limit minus the hysteresis. For example, with a hysteresis of 10% and an activation limit 

of 40%, the level activates with a 40% input signal and switches down to the next lower level with a 30% input signal. 

Automatic switching for certain levels may be disabled by setting an activation limit of 0. The sensor signal will then not 

be able to activate this particular level. This may proof useful for the highest level. (boost mode) 

IP08 defines a reset time after which the unit returns to automatic operation once placed into manual.  

Setting this time to 0, prevents the automatic reset.  

Software configuration 

The MZ3-FU-V11 is designed to work for most comfort ventilation applications. It is however possible to fine tune it to fit 

perfect into the application at hand. The parameters can be changed during operation through an operation unit called 

OPA-S.

 The operating unit OPA-S must be connected for the adjustment of the parameters with the MZ3-FU-V11. This 

connection must not be disconnected earlier than five seconds after the last keystroke.

  

Input configuration 

Parameter 

Description 

Range 

Default 

IP00 

Input signal show percent 

ON, OFF 

ON 

IP01 

Samples taken for averaging input signal 

1…255

 

IP02 

Offset of input signal (Uout = Uset+Offset) 

-

10…10

 

IP03 

Input signal type OFF = 0-10V, ON = 2-10V 

ON, OFF 

OFF 

IP04 

Activation limit for level 1 in auto mode 

0

100% 

40% 

IP05 

Activation limit for level 2 in auto mode.  

Note: Setting this Level to 0, disables it for automatic operation.  

0

100% 

60% 

IP06 

Activation limit for level 3 in auto mode 

Note: Setting this Level to 0, disables it for automatic operation. 

0

100% 

80% 

IP07 

Hysteresis in auto mode. 

0

100% 

10% 

IP08 

Reset time manual to auto 

0: Never reset 

0

255 min 

0 min 

Output configuration 

Parameter 

Description 

Range 

Default 

OP00 

Output level 0  

0

100% 

20% = 2 V 

OP01 

Output level 1, Setting a level to 0 disables it 

0

100% 

40% = 4 V 

OP02 

Output level 2, Setting a level to 0 disables it 

0

100% 

60% = 6 V 

OP03 

Output level 3, Setting a level to 0 disables it 

0

100% 

100% = 10 V 

OP04 

Automatic reset time of the highest level to the level defined in 

OP05. The reset is deactivated with setting = 0 

0…255 min

 

120 min 

OP05 

Output level after automatic reset. This level will be activated 

once the reset time defined in OP04 has expired.  

0…2

 

OP06 

0: Parameter copy successful; No action 

1: Start parameter copy to AEC-PM2 

7: Copy fail (no AEC-PM2 or communication error) 

0-1 

 

7: display only 

 

AUTO-Operation 

Level button 

ON/OFF button 

Содержание MZ3-FU-V11

Страница 1: ...ser and engineering parameters the positioner may be configured to work for most of the standard ventilation applications The device is pre configured according to this documentation Settings such as switching levels of the control curve and ventilation strengths for each Level may be adjusted The configuration may be performed using the programming device called OPA S This device may be used as w...

Страница 2: ...nsing Transport storage Climatic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3K3 and class 1K3 25 70 C 13 158 F 95 RH non condensing class 2MT2 Standards Degree of protection Wall mounted IP40 acc EN 60529 Not installed IP00 acc EN 60529 Safety class III IEC 60536 General Housing material Fireproof ABS PC plastic UL94 class V 0 Dimensions H x W x D in...

Страница 3: ... of the device to keep fan running in minimal volume in OFF mode If JP1 in position 1 2 the output is off in OFF mode Ventilation switches off If JP1 in position 2 3 or removed the output stays in OFF mode in Level 0 minimum air volume View back part when front plate removed New with V2 0 Parameter copy It is now possible to copy settings to an accessory AEC PM2 and to copy them back to other MZ3 ...

Страница 4: ...or the highest level boost mode IP08 defines a reset time after which the unit returns to automatic operation once placed into manual Setting this time to 0 prevents the automatic reset Software configuration The MZ3 FU V11 is designed to work for most comfort ventilation applications It is however possible to fine tune it to fit perfect into the application at hand The parameters can be changed d...

Отзывы: