background image

 

MZ3-FU-V11

 

 

Doc: 70-00-0840 V2.2, 20210628 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alterations 

www.vectorcontrols.com 

Connection diagram 

 

Description:  

Power supply:  

24 VAC, +24 VDC 

Power supply:  

0 V, -24 VDC, internally connected to signal common 

Analog input for sensor 

0…10 VDC

 

Analog output ventilation:  

0…10 VDC

 

Installation and safety advice 

This device is intended to be used as positioner for comfort ventilation systems. Where a device failure endangers human 

life and/or property, it is the responsibility of the client to add additional safety devices to prevent or detect a system 

failure caused by such a device failure.  

The device contains electronic components and must not be disposed of with household waste.

 

Setting of the device to keep fan running in minimal volume in OFF mode 

If JP1 in position 1-2, the output is off in OFF mode. Ventilation switches off.  

If JP1 in position 2-3 or removed, the output stays in OFF mode in Level 0 (minimum air volume)  

View back part when front plate removed 

 

New with V2.0: Parameter copy 

It is now possible to copy settings to an accessory (AEC-PM2) and to copy them back to other MZ3. For this, remove the 

front panel of the MZ3, insert AEC-PM2 in the designated plug. Connect OPA-S and copy parameter from MZ3 to AEC-PM2 

by setting OP06 to 1. 

AEC-

PM2 “Data” LED is ON for 5 seconds after successful parameter copy and OP0

6 is set to 0. If the parameter copy 

failed the LED blinks for 5 seconds and OP06 is set to 7. 

 

Copy parameter from AEC-

PM2 to MZ3 simply by pressing the “Copy” button on the AEC

-PM2. AEC-

PM2 “Data” LED is ON 

for 5 seconds after successful parameter copy. If the parameter copy failed the LED blinks for 5 seconds. 

Содержание MZ3-FU-V11

Страница 1: ...ser and engineering parameters the positioner may be configured to work for most of the standard ventilation applications The device is pre configured according to this documentation Settings such as switching levels of the control curve and ventilation strengths for each Level may be adjusted The configuration may be performed using the programming device called OPA S This device may be used as w...

Страница 2: ...nsing Transport storage Climatic conditions Temperature Humidity Mechanical conditions To IEC 721 3 2 and IEC 721 3 1 class 3K3 and class 1K3 25 70 C 13 158 F 95 RH non condensing class 2MT2 Standards Degree of protection Wall mounted IP40 acc EN 60529 Not installed IP00 acc EN 60529 Safety class III IEC 60536 General Housing material Fireproof ABS PC plastic UL94 class V 0 Dimensions H x W x D in...

Страница 3: ... of the device to keep fan running in minimal volume in OFF mode If JP1 in position 1 2 the output is off in OFF mode Ventilation switches off If JP1 in position 2 3 or removed the output stays in OFF mode in Level 0 minimum air volume View back part when front plate removed New with V2 0 Parameter copy It is now possible to copy settings to an accessory AEC PM2 and to copy them back to other MZ3 ...

Страница 4: ...or the highest level boost mode IP08 defines a reset time after which the unit returns to automatic operation once placed into manual Setting this time to 0 prevents the automatic reset Software configuration The MZ3 FU V11 is designed to work for most comfort ventilation applications It is however possible to fine tune it to fit perfect into the application at hand The parameters can be changed d...

Отзывы: