Read the following applications and comply with them, and your 

MAXX

SST

3000

will give you years of reliable service.

Never connect the inverter’s AC output to an already powered AC distribution system. 

If you will only be operating the 

MAXX

SST

inverter occasionally and manually,

using the two outlets on the front panel of the inverter, then you can disregard the
next two sections (2.1 and 2.2), except for battery charging requirements.

Two primary ways for connecting to an AC distribution system are provided in
sections 2.1 and 2.2. 

2.1 Uninterruptible Power Supply (UPS)

One way is to continuously operate the inverter from the battery bank, simultaneously
replacing the charge on the battery bank using an AC-powered 12 Volt battery
charger or other means of charging the batteries, such as a solar charger system. See

FIGURE 3

. The charger must be selected to operate continuously and to be able to

replace the charge on the battery as the inverter operates. In this configuration, the
battery “floats” on the DC from the charger, not really supplying power or being
charged. When outside AC fails, the inverter continues to power the appliances
for the life of the useful charge on the battery  bank. When outside AC is restored,
the batteries are recharged as the inverter continues to operate. Battery recharging
must be sized to replace the average daily current supplied by the inverter plus a
little more current. Another requirement is that the battery charging rate cannot
exceed 10% of the rated Ampere Hour (AH) rating of the battery bank, otherwise
the life of the batteries can be dramatically reduced through overcharging. Most
modern battery chargers automatically adjust the charging rate based on the state
of the batteries to which they are connected. For this type of operation, use deep
cycle batteries and avoid charging at too fast a rate.

21

5.5.  Permanent Installation  

5.5.1 Preparation for Permanent Installation 

Note than a prepared heavy duty 6 ft. cable kit can be purchased from
your dealer or Vector Manufacturing. Call Tech Support at: 
(954) 584-4446 or (866) 584-5504 Ext. 19 ask for VEC085 cable set.

For permanent installation to heavy-duty battery power you will need:
• Ring terminals to connect two 0000 (4/0) cables to the battery bank
• A single length of not more than ten feet of 0000 (4/0) multi-stranded flexible 

insulated cable

• A 500 ampere low voltage fuse and fuse holder type ANL
• Mounting screws, bolts and nuts for mounting the inverter and the fuse holder
• Tools to drill holes for mounting the inverter and fuse holder
• Lead-tin solder, flux, propane torch and an igniter for the torch
• Sharp utility knife to cut insulation
• Hacksaw to cut the 0000 (4/0) cable
• Pair of diagonal cutters to trim away some cable strands if necessary
• Ring terminals connector for 0000 4/0 cable for connection to battery 

(batteries)

Installation Notes:

The 

MAXX

SST

3000

has four slots in its mounting bracket that allow the unit

to be fastened against a bulkhead, floor, wall or other flat surface. Ideally, the
mounting surface should be cool to the touch. It is more electrically efficient to use
longer AC wiring than DC wiring, so install the inverter as close as possible to the
12 VDC power source.

The inverter can be operated in any position, however, if it is to be mounted on a

wall mount it horizontally so that indicators, switches, outlets and terminal blocks
located on the front panel are visible and accessible.  Look for a convenient place
to mount inverter and the fuse holder. Take the length of cable and do a trial rout-
ing of the cable. Don’t do any cutting at this time. Take a look at 

FIGURE 8

.

Measure the cable path and ensure that either the positive cable run to the battery
or negative cable run to the battery does not  exceed 4 feet. Reposition the 
inverter and fuse holder if necessary. Remember and observe the other 
environmental requirements described earlier. 
After you have selected an appropriate location for the inverter and fuse block,
proceed with the actual installation of the inverter.
Contact Vector™ for any further installation information or questions. Your can purchase
fuses, fuse holders, and 4/0 cable or cable battery connectors from your local 
electrical supplier or from Vector Technical Support at (954) 584-4446 Ext. 19.

5.5.2 Permanent Installation Procedures

The cables between the power source and the inverter should be as shown in

FIGURE 8

. Be sure to remove the carriage bolts before starting permanent installation.

Inverter DC cables and fuse installation is as follows:

Содержание MAXX SST 3000 VEC051

Страница 1: ...d unit of the same or comparable design The repaired or replaced unit will then be warranted under the terms of the remainder of the warranty period The customer is responsible for the shipping charge...

Страница 2: ...THIS POWER INVERTER WARNINGS TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK EXPLOSION OR INJURY Do not connect to AC distribution wiring Remove appliance plug from outlet strip or turn off inverter before...

Страница 3: ...12 VDC battery supply Switch OFF the inverter clean input terminals reconnect input terminals and cable ends reconnect cables Input power source below 10 VDC Recharge or replace power source batterie...

Страница 4: ...inverter shutdown is removed Previously manual reset was required This power inverter also incorporates a new cooling technology that directly benefits our customers The new design more efficiently co...

Страница 5: ...ill automatically shut down until the condition improves FIGURE 2 shows the back panel DC connectors and fan locations Note that the fan only operates when the inverter temperature rises It shuts off...

Страница 6: ...tery configurations with commercial battery chargers or solar battery chargers For most heavy duty applications a multiple battery configuration and the use of deep cycle batteries is a requirement 24...

Страница 7: ...NG NO USER SERVICEABLE COMPONENTS INSIDE OPENING UNIT WILL VOID WARRANTY 23 16 Connect an insulated wire at least 12 AWG between the grounding screw on the inverter s enclosure and a solid electrical...

Страница 8: ...surface that you have selected 2 Mount the fuse holder to its mounting surface using appropriate hardware Ensure that the mounting hardware does not touch any of the fuse holder contacts or fuse conta...

Страница 9: ...battery power you will need Ring terminals to connect two 0000 4 0 cables to the battery bank A single length of not more than ten feet of 0000 4 0 multi stranded flexible insulated cable A 500 amper...

Страница 10: ...e 1 Identify the positive and negative terminals on the 12 volt DC battery and identify the positive and negative terminals on the inverter 2 Remove the plastic terminal cover 3 Using the set of heavy...

Страница 11: ...e ability to operate reactive loads such as those found in inductive motors 19 CAUTIONS This device supplies 110 VAC electrical power directly to the appliances through two standard North American 3 c...

Страница 12: ...llow simultaneous operation of all the AC appliances to be powered with delay characteristics that allow for the momentary high start up current requirements of inductive loads Use the recommended fus...

Страница 13: ...t peak limit the inverter will automatically shut down Once the excessive load is removed the inverter can be restarted and resume normal operation Note If overload shutdown occurs turn OFF the unit a...

Страница 14: ...3 The inverter is in thermal shutdown NOTE It is normal for the alarm to sound when the MAXXSST 3000 is being connected to or disconnected from a 12 VDC power source This does NOT indicate a problem...

Страница 15: ...e indicator will be in the upper red zone Although the inverter has built in protection against overvoltage it may still be damaged if the input voltage exceeds 15 2 volts NOTE Exceeding the recommend...

Страница 16: ...time of 5 minutes but it maintains the temperature of the pot at about 100 watts Typical use of a microwave is only for a few minutes sometimes at low power Some typical exceptions to brief operating...

Отзывы: